Company
Innovationen
Products
The picture may show a similar product.
Part No.: 33623000A
QUADRON®185Power Speed
NH in-line switch-disconnector-fuse size 00
flat version, connection top M8
screw connection, with fuse monitoring
for busbars 30, 40, 60, 80, 100, 120 x 10
not suitable for systems with CrossLink protection modules
System
185Power
Advantages of the product
When the cover is open, all touchable parts are voltage-free
Operator-independent switching
Lockable cover with double-bit lock
Mixed installation with all components 185Power
Can be sealed when switched on or off
Can be locked with up to 3 padlocks when switched off
Product group | 18 |
Subgroup | 52 |
pack size | 1 |
EAN | 4021267336233 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001046 |
ETIM 5.0 | EC001046 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB)
type number: QS185-00
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 160 A |
rated voltage (IEC) AC: | 400 V |
rated isolation voltage Ui AC: | 400 V |
rated surge voltage Uimp : | 4 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B 160A/400V |
cond. short-circuit current with fuses (AC): | 100 kA / 400 V |
120 kA / 400 V | |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 35.2 W.
(The power dissipation at full load would be 55.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
The use of knife links is not permitted. The rated values specified in this product description apply exclusively to the use of fuses. | |
distance to grounded parts = 0mm at 120kA | |
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
Degree of protection IP30 at front, degree of protection near terminal depends on installation |
Mechanical data | |
W x H x D: | 50 x 883 x 222 |
weight: | 448.0 kg/100 |
for busbars: | 30, 40, 60, 80, 100, 120 x 10 |
front degree of protection: | IP30 |
Type of fastening:
can be screwed onto drilled busbar
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
Reference |
Verwendete Variante der Sicherungsüberwachung: IL9075.12/010 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |