Company
Innovationen
Products
The picture may show a similar product.
Part No.: 01562000A
CRITO®30Compact
connection module
with integrated spring terminals 1.5 - 16 mm², AWG 14 - 6
3-pole
for busbars 12 x 5, 10
System
30Compact 3P
Product group | 07 |
Subgroup | 40 |
pack size | 6 |
EAN | 4021267015626 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: M16C-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
rated current (IEC): | 63 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated peak withstand current Ipk max.: | 10 kA |
rated short-time withstand current Icw (0.5 s) max.: | 3 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.0 W.
(The power dissipation at full load would be 0.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 800 V |
max. permitted voltage (IEC) DC: | 800 V |
current capacity (IEC) max.: | 80 A |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 48 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 50 kA |
SCCR: |
50 kA with JDDZ fuse Class J 60 A / 600 V AC
35 kA with any DIVQ/7 circuit breaker 60 A / 480 V AC |
Mechanical data | |
W x H x D: | 20 x 160 x 91 |
weight: | 16.0 kg/100 |
poles: | 3-pole |
for busbars: | 12 x 5, 10 |
Terminal points | |
min. cross-section: | 1.5 mm² |
max. cross-section: | 16 mm² |
Not suitable for aluminium cables ! | |
for leads as per IEC : |
Not suitable for aluminium cables ! | |
The insulation performance of the article depends on the installation conditions. | |