switch disconnector with fuses, 3-pole

The picture may show a similar product.

Description

Part No.: 33510 000

QUADRON 60Classic Speed

switch disconnector with fuses, 3-pole

screw M10, connection bottom

size 1

double-breaking

operator independent switching (snap-action mechanism)

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Can be locked in neutral position with up to 3 padlocks
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch).

CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat rails

Product group 15
Subgroup 23
pack size 1
EAN 4021267335106
ECLASS 14.0 27371401
ETIM 5.0 EC001040
ETIM 8.0 EC001040
ETIM 10.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB) , VDE , DNV GL

type number: QCS-NH1

EAC Type: NH

Technical data

for fuse links size: NH 1
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 23 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 250 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 8 kV
Utilisation category AC (IEC 60947-3) : AC-23B (690V, 250A)
AC-23A (500V, 250A)
AC-22A (690V, 250A)
cond. short-circuit current with fuses (AC): 50 kA / 690V
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 52.5 W.

(The power dissipation at full load would be 82.0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted operation temperature 55°C
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
System component: degree of protection IP20 at front as per DIN EN 60529, degree of protection near terminal depends on installation; shock protection as per DIN EN 50274

adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe)
Mechanical data
W x H x D: 184 x 286 x 194
weight: 567.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars.

When installing QCS, a busbar support is to be applied left and right, see assembly manual.

Terminal points
screw connection
M10
screw drive: SW16
Md min.: 30.0 Nm
Md max.: 35.0 Nm
Material properties
halogen-free: No

Application notes

permitted power dissipation of the fuse-link: 23 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.

Links (Prices, CAD data)

Downloads

Accessories

connection accessories

33145 000
prism terminal, double, for Cu cables
2x 35 - 70 mm²
for: QCB-NH1, QCS-NH1, QCS-320
More

33163 000
clamp connector for Cu cables
70 - 150 mm²
for: QCB-NH2, LTS-F 400, LTS 630
More

33166 000
prism terminal, single, for Cu cables
35 - 150 mm²
QCB-NH1, QCS-NH1, QCS-320
for: QCB-NH1, QCS-NH1, QCS-320
More

33909 000
box terminal for Cu cables
35 - 150 mm²
QCB-NH1, QCS-NH1, QCS-320
for: QCB-NH1, QCS-NH1, QCS-320
More

covers

33142 000
cover for cable lugs, top / bottom attachable
for: QCB-NH1, QCS-NH1, QCS-320
More

further accessories

33908 000
pilot switch for monitoring the switch position
changeover 250 V AC / 5 A, 30 V DC / 4 A
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com