Part No.: 01135000
CRITO®
brace terminal
35 - 150 mm², AWG 2 - 300 MCM, lam. Cu. 15 - 20 x 5 - 10
for busbars 12, 15, 20 x 5, 10
System
60Classic, 30Compact 3P
Advantages of the product
Terminal with captive clamping screws, conductor can be overlapped.
Indication of nominal cross-section and tightening torque noted on the terminal.
Contact between conductor and busbar via cable bed.
Product group | 07 |
Subgroup | 19 |
pack size | 6 |
EAN | 4021267011352 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: 515-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
rated current (IEC): | 275 A |
rated voltage (IEC) AC: | 690 V |
rated peak withstand current Ipk max.: | 49.8 kA |
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 1000 V |
max. permitted voltage (IEC) DC: | 1500 V |
current capacity (IEC) max.: | 480 A |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 285 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR: | 18 kA |
Mechanical data | |
W x H x D: | 28 x 34 x 69 |
weight: | 10.2 kg/100 |
for busbars: | 12, 15, 20 x 5, 10 |
Terminal points | |
min. cross-section: | 35 mm² |
max. cross-section: | 150 mm² |
Terminal space: | 20 x 22 |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
for applications acc. to IEC / EN : |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
The insulation performance of the article depends on the installation conditions. | |
for UL feeder circuits >250V |