Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31588000A
SECUR®60Classic EasyLiner
seccionador-interruptor-fusível D0 em barramento 5 polos
Para fusíveis D01 e D02, para sistemas de barramento 250 A, 400 A e 630 A da empresa Hensel
E18 / 63 A / 3P
operator independent switching (snap-action mechanism)
connection bottom
para barramentos 12, 20, 30 x 5, 10
Sistema
60Classic
Vantagens do produto
spring terminal enables connection without tools (at first installation)
Grupo de produto | 01 |
Subgroup | 42 |
Unidade por pacote | 1 |
EAN | 4021267315887 |
catalog page | 2020 : 3.19 |
ECLASS 6.1 | 27142110 |
ECLASS 7.1 | 27142110 |
ETIM 4.0 | EC000277 |
ETIM 5.0 | EC000277 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , VDE , CCC
Número de tipo: SEL
CCC certificate: 2014010302710123
for fuse links size: | D0 |
fuse links acc. to standard: | IEC / HD 60269-3 |
permitted power dissipation of the fuse-link: | 5,5 W |
requirements for contact parts: | use fuse links with silver-plated contacts |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 63 A |
Tensão de medição (IEC) AC: | 400 V |
rated frequency (IEC): | 50 / 60 Hz |
Tensão nominal de isolamento: | 500 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-22B (400 V) |
cond. short-circuit current with fuses (AC): | 50 kA / 400 V |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 4,5 W.
(A dissipação de energia em sua carga máxima seria 7,0 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
reduction factor at ambient temperature: 35°C 1,0 45°C 0,9 55°C 0,8 |
|
for fuse links and gauge elements acc. to IEC / HD 60269-3 use of D02 fuse links with silver plated caps is recommended |
|
The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard. |
Dados mecânicos | |
L x A x P: | 27 x 200 x 80 |
Peso: | 33,0 kg/100 |
Polaridade: | 3 polos |
para barramentos: | 12, 20, 30 x 5, 10 |
front degree of protection: | IP20 |
pontos terminais | |
spring pulley connection | |
screw drive: | PZ2 |
wire stripping: | 12 mm |
min. cross-section: | 1,5 mm² |
max. cross-section: | 16 mm² |
Md min.: | 2,5 Nm |
Md max.: | 3,0 Nm |
Not suitable for aluminium cables ! | |
1,5 - 16 mm² round stranded and flexible without wire-end ferrule |
Notas
The devices have to be equipped with D0 gauge rings. Together with reducer part no. 31902 also suitable for fuse links D01.
The use of the side module part no. 31914 is recommended for continuous loads of 35 A or greater..
use of D02 fuse links with silver plated caps is required
can be locked (padlock) in OFF position (O) and sealed in ON position (1)
can be used in 5-pole busbar systems 250 A, 400 A and 630 A of company Hensel.
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com