Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31296000
AMBUS®Panel
suporte para fusíveis cilíndricos
Class CC / 2P
30 A / 600 V
for mounting rail
Sistema
Panel
Vantagens do produto
large clamping range, also for two identical conductors (adjacent)
holder for label
Grupo de produto | 17 |
Subgroup | 07 |
Unidade por pacote | 6 |
EAN | 4021267312961 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system J
UL 4248-1
UL 4248-4
Approvals
CSA , UL , CCC
for UL feeder circuits >250V
Número de tipo: AESCC
UL file: E230163, UL category (for USA): IZLT https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com
CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org
CCC certificate: 21107299296
for fuse links size: | Class CC |
fuse links acc. to standard: | UL 248-4 |
permitted power dissipation of the fuse-link: | 4 W |
Dados IEC | |
Standards | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016, Fuse system J |
Electrical data
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 0,4 W.
(A dissipação de energia em sua carga máxima seria 0,6 W.)
Dados UL | |
Standards | |
UL 4248-1
UL 4248-4 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Dados electricos UL | |
corrente nominal (UL): | 30 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
tensão nominal (UL) DC: | 600 V |
SCCR: | 200 kA |
Dados mecânicos | |
L x A x P: | 36 x 81 x 58 |
Peso: | 11,3 kg/100 |
Polaridade: | 2 polos |
Montagem: | for mounting rail |
degree of protection: | IP20 |
front degree of protection: | IP20 |
pontos terminais | |
cage clamp connection | |
screw drive: | PZ2 |
wire stripping: | 11 mm |
min. cross-section: | 0,75 mm² |
max. cross-section: | 25 mm² |
Md min.: | 2,0 Nm |
Md max.: | 2,5 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 18 |
max. cross-section UL: | AWG 4 |
for applications acc. to IEC / EN : |
Not suitable for aluminium cables ! | |
permitted power dissipation of the fuse-link: | 4 W |
for UL feeder circuits >250V |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com