Inovações
Produtos
for UL feeder circuits >250V
A imagem pode mostrar um produto similar.
Código da peça: 01595 000A
CRITO®CrossBoard
módulo de conexão
grampo 150 mm²
3 polos
Conexão superior ou inferior
para CrossBoard 250 A 300 - 1100 mm
Sistema
CrossBoard® 125A / 250A
| Grupo de produto | 07 |
| Subgroup | 48 |
| Unidade por pacote | 1 |
| EAN | 4021267015954 |
| ECLASS 6.1 | 27141146 |
| ECLASS 7.1 | 27141146 |
| ETIM 4.0 | EC000001 |
| ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
UL
for UL feeder circuits >250V
Número de tipo: CR-B-114-A1
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Aprovação CCC: no certification required
| Dados IEC | |
| Standards | |
|
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
| Dados elétricos IEC | |
| Corrente de medição (IEC): | 250 A |
| Tensão de medição (IEC) AC: | 690 V |
| Tensão nominal de isolamento: | 800 V |
| Tensão suportável nominal de impulso Uimp: | 6 kV |
| rated peak withstand current Ipk max.: | 30 kA |
| Dados adicionais IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| tensão máxima IEC AC: | 800 V |
| tensão máxima IEC DC: | 800 V |
| current capacity (IEC) max.: | 250 A |
| Dados UL | |
| Standards | |
| UL 508 |
| for UL feeder circuits >250V | |
| suitable for field-installed conductors |
| Dados electricos UL | |
| corrente nominal (UL): | 285 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| for wires UL: | Cu 75°C |
| SCCR unprotected max.: | 10 kA |
| 3 cycles (without OPD) @ 600 V AC | |
| SCCR protected max.: | 100 kA |
| SCCR: |
100 kA with JDDZ fuse Class J 400 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
| Dados mecânicos | |
| L x A x P: | 114 x 222 x 57 |
| Peso: | 96,4 kg/100 |
| Polaridade: | 3 polos |
| front degree of protection: | IP20 |
| pontos terminais | |
| prism terminal | |
| screw drive: | S4 |
| wire stripping: | 30 mm |
| min. cross-section: | 35 mm² |
| max. cross-section: | 150 mm² |
| Md min.: | 4,0 Nm |
| Md max.: | 6,0 Nm |
|
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| min. cross-section UL: | AWG 2 |
| max. cross-section UL: | MCM 300 |
| torque (UL): | 35 - 53 lb-in |
| for wires UL: | Cu 75°C |
|
Connecting circular conductors: |
|
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| The insulation performance of the article depends on the installation conditions. | |
|
Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation |
|
| for UL feeder circuits >250V |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com