Inovações
Produtos
Ferramentas
for UL feeder circuits >250V
A imagem pode mostrar um produto similar.
Código da peça: 31138000
AMBUS®Panel
suporte para fusíveis cilíndricos, com LED
14 x 51 / 3P
50 A / 110 - 690 V
indication of a released fuse link
für DIN Tragschiene
Sistema
DIN rail
Vantagens do produto
large clamping range
holder for label
with indicator for tripped fuse
any polarity for DC voltage
Grupo de produto | 17 |
Subgroup | 09 |
UE | 2 |
EAN | 4021267311384 |
catalog page | 2020 : 6.6 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approvals
CSA , UL , CCC , EAC
for UL feeder circuits >250V
Número de tipo: AES14x51
EAC Type: AES
UL file: E230163, UL category (for USA): IZLT https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com
CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org
CCC certificate: 2012010302584095
for fuse links size: | 14x51 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 5 W |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 50 A |
Tensão de medição (IEC) AC: | 690 V |
min. operating voltage AC: | 110 V |
min. operating voltage DC: | 110 V |
Tensão nominal de isolamento: | 690 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
cond. short-circuit current with fuses (AC): | 100 kA / 400 V (50 A) |
100 kA / 500 V (40 A) | |
80 kA / 690 V (25 A) | |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 1,7 W.
(A dissipação de energia em sua carga máxima seria 2,7 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
tensão máxima IEC AC: | 725 V |
further utilisation category AC (IEC 60947-3): | AC-20B (1000 V) at pollution degree 2 |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
for fuse links as per IEC / EN 60269-2 with permitted rated power dissipations up to max. 5W for gG/gL up to max. 3W for aM indicator light operating voltage range: 110 - 690V AC / DC |
Dados UL | |
Standards | |
UL 4248-1 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Dados electricos UL | |
rated current (UL): | 50 A |
rated voltage (UL) AC: | 600 V |
min. operating voltage AC: | 110 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
min. operating voltage DC: | 110 V |
for wires UL: | Cu 75°C |
SCCR: | 100 kA |
Dados mecânicos | |
L x A x P: | 81 x 90 x 69 |
Peso: | 30,5 kg/100 |
Polaridade: | 3 polos |
Mounting: | für DIN Tragschiene |
degree of protection: | IP20 |
front degree of protection: | IP20 |
pontos terminais | |
cage clamp connection | |
wire stripping: | 14 mm |
min. cross-section: | 1,5 mm² |
max. cross-section: | 35 mm² |
Md min.: | 2,5 Nm |
Md max.: | 3,0 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 14 |
max. cross-section UL: | AWG 2 |
torque (UL): | 26 lb-in |
for wires UL: | Cu 75°C |
box terminal : |
Notas
The indicator light signals that the fuse has tripped, but only when the closed fuse-holder is under voltage.
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508