Inovações
Produtos
Ferramentas
for UL feeder circuits >250V
A imagem pode mostrar um produto similar.
Código da peça: 31973000
AMBUS®Panel
suporte para fusíveis cilíndricos
10x38 / 1P / LED
30 A / 1000 V DC
indication of a released fuse link
für DIN Tragschiene
Sistema
DIN rail
Vantagens do produto
large clamping range
holder for label
Grupo de produto | 17 |
Subgroup | 06 |
UE | 12 |
EAN | 4021267319731 |
catalog page | 2020 : 6.7 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016
UL 4248-1
UL 4248-19
Approvals
IEC (CB) , CSA , UL , CCC , EAC
for UL feeder circuits >250V
Número de tipo: AES10x38/PV
EAC Type: AES
UL file: E342576, UL category (for USA): IZMR https://www.ul.com
CSA file: 110285, CSA class: 6225-30 https://directories.csa-international.org
CCC certificate: 2013010308601276
for fuse links size: | 10x38 |
fuse links acc. to standard: | IEC / EN 60269-6 |
permitted power dissipation of the fuse-link: | 4 W |
Dados IEC | |
Standards | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016 |
Dados elétricos IEC | |
Corrente de medição (IEC): | 30 A |
Tensão de medição (IEC) DC: | 1000 V |
min. operating voltage DC: | 400 V |
rated isolation voltage Ui DC: | 1000 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
cond. short-circuit current with fuses (DC): | 20 kA / 1000 V (30 A) |
approved wth fuse links of operation class: | gPV |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 0,2 W.
(A dissipação de energia em sua carga máxima seria 0,3 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
tensão máxima IEC DC: | 1000 V |
use of fuse links with silver plated caps is recommended |
Dados UL | |
Standards | |
UL 4248-1
UL 4248-19 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Dados electricos UL | |
rated current (UL): | 30 A |
rated voltage (UL) DC: | 1000 V |
min. operating voltage DC: | 400 V |
for wires UL: | Cu 90°C |
SCCR protected max.: | 33 kA |
with IZLT fuse 10x38 30 A / 1000 V DC | |
max. let-through current Id (UL): | 8,65 kA |
max. let-trough energy (UL): | 16,9 kA²s |
Dados mecânicos | |
L x A x P: | 18 x 81 x 58 |
Peso: | 5,7 kg/100 |
Polaridade: | 1 polo |
Mounting: | für DIN Tragschiene |
degree of protection: | IP20 |
front degree of protection: | IP20 |
pontos terminais | |
cage clamp connection | |
screw drive: | PZ2 |
wire stripping: | 11 mm |
min. cross-section: | 0,75 mm² |
max. cross-section: | 25 mm² |
Md min.: | 2,0 Nm |
Md max.: | 2,5 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 18 |
max. cross-section UL: | AWG 4 |
torque (UL): | 18 - 22 lb-in |
for wires UL: | Cu 90°C |
for applications acc. to IEC / EN : |
Notas
The indicator light signals that the fuse has tripped, but only when the closed fuse-holder is under voltage.
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com