seccionador-interruptor-fusível (31660)

A imagem pode mostrar um produto similar.

Descrição

Código da peça: 31660 000A

SECUR®Crossboard

seccionador-interruptor-fusível

Size D02 / E 18

para fusíveis D01 e D02

35 A / 3P

operator independent switching (snap-action mechanism)

connection bottom

NEW

Sistema

CrossBoard® 125A / 250A, CrossBoard® 800 A

Vantagens do produto

spring terminal enables connection without tools (at first installation)

Grupo de produto 01
Subgroup 51
Unidade por pacote 1
EAN 4021267316600
ETIM 5.0 EC000277
ETIM 8.0 EC000277

Aprovações

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB) , VDE

Dados técnicos

for fuse links size: D0
fuse links acc. to standard: IEC / HD 60269-3
permitted power dissipation of the fuse-link: 4 W
Dados IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Dados elétricos IEC
Corrente de medição (IEC): 35 A
Tensão de medição (IEC) AC: 400 V
Tensão nominal de isolamento: 500 V
Tensão suportável nominal de impulso Uimp: 6 kV
Utilisation category AC (IEC 60947-3) : AC-22B (400 V)
cond. short-circuit current with fuses (AC): 50 kA / 400 V
approved wth fuse links of operation class: gG
Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
max. permitted operation temperature 45°C

The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard.

Dados mecânicos
L x A x P: 22.5 x 184 x 100
Peso: 33,0 kg/100
Polaridade: 3 polos
front degree of protection: IP30
pontos terminais
spring pulley connection
screw drive: 0,8x4
wire stripping: 23 mm
min. cross-section: 2,5 mm²
max. cross-section: 16 mm²
f: 2.5 - 16 mm²
Not suitable for aluminium cables !
Material properties
halogen-free: Yes

Instruções de Aplicação

Not suitable for aluminium cables !
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
permitted power dissipation of the fuse-link: 4 W

Links

Downloads

Encontre sua pessoa de contato

Para a página de contato

Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil

Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de

Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com