Código da peça: 31262 000A
SECUR®Crossboard
seccionador-interruptor-fusível
para fusíveis 10x38 IEC 60269-2
3P
indication (LED) of a tripped fuse link
operator independent switching (snap-action mechanism)
connection bottom
NEW
Sistema
CrossBoard® 125A / 250A, CrossBoard® 800 A
Vantagens do produto
spring terminal enables connection without tools (at first installation)
| Grupo de produto | 01 | 
| Subgroup | 52 | 
| Unidade por pacote | 1 | 
| EAN | 4021267312626 | 
| ECLASS 6.1 | 27371401 | 
| ECLASS 7.1 | 27371401 | 
| ETIM 4.0 | EC001040 | 
| ETIM 5.0 | EC001040 | 
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , VDE
																		
																		
| for fuse links size: | 10x38 | 
| fuse links acc. to standard: | IEC / HD 60269-2 | 
| permitted power dissipation of the fuse-link: | 3 W | 
| Dados IEC | |
| Standards | |
| 
																		IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only  | 
																
| Dados elétricos IEC | |
| Corrente de medição (IEC): | 32 A | 
| Tensão de medição (IEC) AC: | 690 V | 
| Tensão nominal de isolamento: | 800 V | 
| rated isolation voltage Ui DC: | 250 V | 
| Tensão suportável nominal de impulso Uimp: | 6 kV | 
| Utilisation category AC (IEC 60947-3) : | AC-23 A (400 V)  | 
															
| cond. short-circuit current with fuses (AC): | 100 kA / 400 V (32A) | 
| approved wth fuse links of operation class: | gG | 
| Dados adicionais IEC | |
| 
																	 The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.  | 
															
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | 
The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard.  | 
															
| Dados mecânicos | |
| L x A x P: | 22.5 x 184 x 100 | 
| Peso: | 33,0 kg/100 | 
| Polaridade: | 3 polos | 
| front degree of protection: | IP30 | 
| pontos terminais | |
| spring pulley connection | |
| screw drive: | 0,8x4 | 
| wire stripping: | 23 mm | 
| min. cross-section: | 2,5 mm² | 
| max. cross-section: | 16 mm² | 
| f: | 2.5 - 16 mm² | 
| Not suitable for aluminium cables ! | |
| Not suitable for aluminium cables ! | |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
| permitted power dissipation of the fuse-link: | 3 W | 
						
                31976
        000A
        
        
            interruptor de sinalização
            
            
            comutador 250 250 V AC / 5 A, 30 V DC / 4 A
            
            
        Mais
        
						
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com