Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 33778000A
QUADRON®185Power
módulo para 4x chave seccionadora com base porta fusível NH, 3 polos
4x NH 000 (max. 63 A)
for systems with drilled busbars
para barramentos 30, 40, 60, 80, 100, 120 x 10
NEW
Sistema
185Power
Vantagens do produto
Schienenträger überbaubar (in Systemen mit und ohne Crosslink Berührungsschutzabdeckungen)
Grupo de produto | 09 |
Subgroup | 37 |
Unidade por pacote | 1 |
EAN | 4021267337780 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
for fuse links size: | NH 000 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 9 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 252 A |
Tensão de medição (IEC) AC: | 690 V |
Tensão de medição (IEC) DC: | 440 V |
Tensão nominal de isolamento: | 800 V |
rated isolation voltage Ui DC: | 500 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-21B (690 V / 80 A) AC-22B (400 V / 125 A) |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 65,9 W.
(A dissipação de energia em sua carga máxima seria 103,0 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
|
Dados mecânicos | |
L x A x P: | 99 x 672 x 186 |
Peso: | 552,5 kg/100 |
Polaridade: | 3 polos |
para barramentos: | 30, 40, 60, 80, 100, 120 x 10 |
Montagem: | for systems with drilled busbars |
CT can be integrated in the device: | ja |
front degree of protection: | IP20 |
Montagem de instalação vertical: | Sim |
Montagem de instalação horizontal: | Não |
for fuse links max. 21 mm wide
pontos terminais | |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
tunnel terminal 1.5 - 50 mm² |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
Notas |
for use with horizontal busbar systems |
permitted power dissipation of the fuse-link: | 9 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |