Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31579000B
SECUR®60Classic EasyLiner
seccionador-interruptor-fusível D0 para montagem em barramento 5 polos
para fusíveis D01 e D02, com LED
E18 / 63 A / 3P
operator independent switching (snap-action mechanism)
connection bottom
para barramentos 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção
Sistema
60Classic
Vantagens do produto
spring terminal enables connection without tools (at first installation)
Grupo de produto | 01 |
Subgroup | 42 |
Unidade por pacote | 1 |
EAN | 4021267315795 |
ECLASS 6.1 | 27142110 |
ECLASS 7.1 | 27142110 |
ETIM 4.0 | EC000277 |
ETIM 5.0 | EC000277 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , VDE , CCC
Número de tipo: SEL
CCC certificate: 2014010302710123
for fuse links size: | D0 |
fuse links acc. to standard: | IEC / HD 60269-3 |
permitted power dissipation of the fuse-link: | 5,5 W |
requirements for contact parts: | use fuse links with silver-plated contacts |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 63 A |
Tensão de medição (IEC) AC: | 400 V |
rated frequency (IEC): | 50 / 60 Hz |
Tensão nominal de isolamento: | 500 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-22B (400 V) |
cond. short-circuit current with fuses (AC): | 50 kA / 400 V |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 4,5 W.
(A dissipação de energia em sua carga máxima seria 7,0 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
reduction factor at ambient temperature: 35°C 1,0 45°C 0,9 55°C 0,8 |
|
for fuse links and gauge elements acc. to IEC / HD 60269-3 use of D02 fuse links with silver plated caps is recommended |
|
The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard. |
Dados mecânicos | |
L x A x P: | 27 x 200 x 80 |
Peso: | 33,0 kg/100 |
Polaridade: | 3 polos |
para barramentos: | 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção |
front degree of protection: | IP20 |
pontos terminais | |
spring pulley connection | |
screw drive: | PZ2 |
wire stripping: | 12 mm |
min. cross-section: | 1,5 mm² |
max. cross-section: | 16 mm² |
Md min.: | 2,5 Nm |
Md max.: | 3,0 Nm |
Not suitable for aluminium cables ! | |
1,5 - 16 mm² round stranded and flexible without wire-end ferrule |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
Notas |
The devices have to be equipped with D0 gauge rings. Together with reducer part no. 31902 also suitable for fuse-links D01. |
permitted power dissipation of the fuse-link: | 5,5 W |
requirements for contact parts: | use fuse links with silver-plated contacts |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com