Código da peça: 33593 100A
QUADRON 185Power
chave seccionadora de fusível vertical 160 A
high version with box terminal 70 mm²
Tamanho 00, comutável 3 polos
para barramentos 30, 40, 60, 80, 100, 120 x 10
NEW
Sistema
185Power
Vantagens do produto
Self-closing inspection holes are available in the cover.
Cover can be locked when closed.
| Grupo de produto | 12 |
| Subgroup | 52 |
| Unidade por pacote | 60 |
| EAN | 4021267151027 |
| ETIM 5.0 | EC001046 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , CCC
Número de tipo: QU185-00
EAC Type: NH
CCC certificate: 2015010302769751
| for fuse links size: | NH 000, NH 00 |
| fuse links acc. to standard: | IEC / HD 60269-2 |
| permitted power dissipation of the fuse-link: | 12 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
| Dados IEC | |
| Standards | |
|
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
| Dados elétricos IEC | |
| Corrente de medição (IEC): | 160 A |
| Tensão de medição (IEC) AC: | 800 V |
| Tensão nominal de isolamento: | 1000 V |
| Tensão suportável nominal de impulso Uimp: | 8 kV |
| Utilisation category AC (IEC 60947-3) : | AC-22B (800 V / 63 A) |
| cond. short-circuit current with fuses (AC): | 30 kA / 800 V (63 A) |
| 100 kA / 690 V | |
| approved wth fuse links of operation class: | gG |
| short-circuit strength when protected by fuses: | 100 kA |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 17,9 W.
(A dissipação de energia em sua carga máxima seria 28,0 W.)
| Dados adicionais IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| tensão máxima IEC DC: | 1000 V |
| further utilisation category DC (IEC 60947-3): | DC-20B max. voltage between the fuses: 1000V visible information required: Do not switch under load. |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
| min. permitted operation temperature | -40°C |
| max. permitted operation temperature | 55°C |
| min. permitted temperature for transport and storage | -40°C |
| Degree of protection IP20 at front, degree of protection near terminal depends on installation |
| Dados mecânicos | |
| L x A x P: | 50 x 670 x 189 |
| Peso: | 261,8 kg/100 |
| para barramentos: | 30, 40, 60, 80, 100, 120 x 10 |
| CT can be integrated in the device: | ja |
| front degree of protection: | IP20 |
| degree of protection when open: | IP20 |
| pontos terminais | |
| cage clamp connection | |
| screw drive: | S4 |
| wire stripping: | 20 mm |
| min. cross-section: | 1,5 mm² |
| max. cross-section: | 70 mm² |
| re: | 1.5 - 10 mm² |
| rm: | 16 - 70 mm² |
| f: | 1.5 - 70 mm² |
| f + AE: | 1.5 - 70 mm² |
| (f + AE may not fit with max. cross-section) | |
| Md min.: | 5,0 Nm |
| Md max.: | 6,0 Nm |
| lam. Cu width: | 9 - 12 mm |
| lam. Cu thickness: | 2 - 10 mm |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
| permitted power dissipation of the fuse-link: | 12 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |