Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31555000
SECUR®Panel
suporte para fusíveis cilíndricos
10 x 85 / 1P
32 A, 1500 V DC
for mounting rail
Sistema
Panel
Vantagens do produto
easy replacement of the fuse-link
front degree of protection IP20 always guaranteed
Grupo de produto | 17 |
Subgroup | 18 |
Unidade por pacote | 5 |
EAN | 4021267315559 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016
UL 4248-1
UL 4248-19
Approvals
UL
Número de tipo: AES10x85
UL file: E342576, UL category (for USA): IZMR https://www.ul.com
for fuse links size: | 10x85 |
fuse links acc. to standard: | IEC / EN 60269-6 |
permitted power dissipation of the fuse-link: | 6 W |
Dados IEC | |
Standards | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016 |
Dados elétricos IEC | |
Corrente de medição (IEC): | 32 A |
Tensão de medição (IEC) AC: | 1000 V |
Tensão de medição (IEC) DC: | 1500 V |
Tensão suportável nominal de impulso Uimp: | 8 kV |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 0,2 W.
(A dissipação de energia em sua carga máxima seria 0,3 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
for fuse links 10x85 or 14x85 as per IEC 60269-2, -4, -6 with permitted rated power dissipations up to max. 6.0W |
Dados UL | |
Standards | |
UL 4248-1
UL 4248-19 |
Dados electricos UL | |
corrente nominal (UL): | 30 A |
tensão nominal (UL) DC: | 1500 V |
SCCR: | 15 kA |
Dados mecânicos | |
L x A x P: | 22.5 x 130 x 65 |
Peso: | 9,2 kg/100 |
Polaridade: | 1 polo |
Montagem: | for mounting rail |
front degree of protection: | IP20 |
pontos terminais | |
cage clamp connection | |
screw drive: | PZ2 |
wire stripping: | 11 mm |
min. cross-section: | 0,75 mm² |
max. cross-section: | 25 mm² |
Md min.: | 2,0 Nm |
Md max.: | 2,5 Nm |
Not suitable for aluminium cables ! | |
Box terminal |
Not suitable for aluminium cables ! | |
The insulation performance of the article depends on the installation conditions. | |
Notas |
Min. permitted ambient temperature: -25°C (installation only at temperatures > -5°C) |
permitted power dissipation of the fuse-link: | 6 W |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com