            Company
            
        
        
            Innovations
            
        
        
      
        
            Products
            
        
      	
        
        
        
    The picture may show a similar product.
Part No.: 11300 000A
CrossBoard®
basic system 250 A
3-pole
300 mm long, touch-safe protected
with CrossLink® interface
NEW
System
CrossBoard® 125A / 250A
Advantages of the product
touch-safe protected busbar system up to 250 A
rear feedable
plug and play
easy to screw to mounting plates
completely pre-assembled and immediately ready for use
| Product group | 06 | 
| Subgroup | 50 | 
| pack size | 1 | 
| EAN | 4021267113001 | 
| ECLASS 6.1 | 27400613 | 
| ECLASS 7.1 | 27400613 | 
| ETIM 4.0 | EC001900 | 
| ETIM 5.0 | EC001900 | 
Standards
IEC 61439-1:2020
UL 508
Approvals
IEC (CB) , UL
																		 
																		 
for UL feeder circuits >250V
type number: CB-XL-300-24x16
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 | 
| Electrical data IEC | |
| rated current (IEC): | 250 A | 
| rated voltage (IEC) AC: | 690 V | 
| rated isolation voltage Ui AC: | 800 V | 
| rated surge voltage Uimp : | 6 kV | 
| rated peak withstand current Ipk max.: | 30 kA | 
| rated short-time withstand current Icw (0.1 s) max.: | 15 kA | 
| Supplementary data IEC | |
| The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. | 
| max. permitted voltage (IEC) DC: | 800 V | 
| Details UL | |
| Standards | |
| UL 508 | 
| for UL feeder circuits >250V | 
| Electrical data UL | |
| rated current (UL): | 250 A | 
| rated voltage (UL) AC: | 600 V | 
| rated frequency (UL): | 50 / 60 Hz | 
| rated voltage (UL) DC: | 600 V | 
| SCCR unprotected max.: | 10 kA | 
| 3 cycles (without OPD) @ 600 V AC | |
| SCCR protected max.: | 100 kA | 
| with JDDZ fuse Class J 400 A / 600 V AC | 
| SCCR: | 65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC 100 kA with JDDZ fuse Class J 400 A / 600 V AC | 
| Mechanical data | |
| W x H x D: | 300 x 160 x 45 | 
| weight: | 129,8 kg/100 | 
| poles: | 3-pole | 
| degree of protection: | IP20 | 
| Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation | |
| for UL feeder circuits >250V | 
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com