Company
Innovations
Products
The picture may show a similar product.
Part No.: 36200000A
BROOME10®CrossBoard
power supply 10 A
400 V AC / 24 V DC, with push-in terminals
System
CrossBoard® 125A / 250A, CrossBoard® 800 A
Advantages of the product
direct installation to CrossBoard®
efficiency of 95% permits an intallation width of 45 mm
self-protected at short-circuit with intelligent re-start
no pre-fuse needed
overvoltage capacity up to 6 kV
Product group | 21 |
Subgroup | 40 |
pack size | 1 |
EAN | 4021267362003 |
ECLASS 6.1 | 27142325 |
ECLASS 7.1 | 27142325 |
ETIM 4.0 | EC002540 |
ETIM 5.0 | EC002540 |
Standards
IEC 61010-1:2010
IEC 61010-2-201:2013
UL 61010-1
UL 61010-2-201
Approvals
IEC (CB) , UL
for UL feeder circuits >250V
type number: BROOME10
UL file: E497002, UL category (for USA): NMTR. https://www.ul.com
UL file: E497002, UL category (for Canada): NMTR7. https://www.ul.com
Details IEC | |
Standards | |
IEC 61010-1:2010 IEC 61010-2-201:2013 |
Electrical data IEC | |
rated voltage (IEC) AC: | 480 V |
min. operating voltage AC: | 380 V |
output voltage DC: | 24 V |
output current: | 10 A |
voltage control: | No |
typical hold-up time (400 V): | 20 ms |
typical hold-up time (480 V): | 20 ms |
separation input / output: | SELV / PELV |
over-voltage protection: | 32 V |
parallel operation possible: | Yes |
serial operation possible: | Yes |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
2-pole feeding at L1 and L2 |
Details UL | |
Standards | |
UL 61010-1
UL 61010-2-201 |
for UL feeder circuits >250V |
Electrical data UL | |
rated voltage (UL) AC: | 480 V |
min. operating voltage AC: | 380 V |
rated frequency (UL): | 50 / 60 Hz |
Mechanical data | |
W x H x D: | 45 x 160 x 130 |
weight: | 71,8 kg/100 |
poles: | 3-pole |
degree of protection: | IP30 |
Terminal points | |
push-in connection | |
screw drive: | 0,5x3 |
wire stripping: | 10 mm |
min. cross-section: | 0,2 mm² |
max. cross-section: | 2,5 mm² |
min. cross-section UL: | AWG 24 |
max. cross-section UL: | AWG 12 |
f+AE max. 1,5 mm² |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com