Part No.: 32784000A
EQUES®185Power
busbar adapter 1220 A
300 x 652, connection top / bottom, screw connection
for ABB Tmax T7, XT7 (1250 A), Emax E1.2 (1250 A), Siemens 3VA27 (1250 A)
for busbars 30, 40, 60, 80, 100, 120 x 10
not suitable for systems with CrossLink protection modules
System
185Power
Product group | 05 |
Subgroup | 48 |
pack size | 1 |
EAN | 4021267327842 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: EQ185-A1600-S
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 1220 A |
rated voltage (IEC) AC: | 690 V |
rated voltage (IEC) DC: | 800 V |
rated isolation voltage Ui AC: | 1000 V |
rated isolation voltage Ui DC: | 1000 V |
rated surge voltage Uimp : | 12 kV |
rated peak withstand current Ipk max.: | 106 kA |
rated short-time withstand current Icw (1.0 s) max.: | 50 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 221,4 W.
(The power dissipation at full load would be 346,0 W.)
mit ABB Tmax T7 1250A bis 1220A Verbindung unten einsetzbar! mit ABB Tmax T7 1250A bis 1250A Verbindung oben einsetzbar! |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 1200 A |
rated voltage (UL) AC: | 1000 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 50 kA |
3 cycles (without OPD) @ 1000 V AC |
Mechanical data | |
W x H x D: | 300 x 652 x 85 |
weight: | 2800,0 kg/100 |
poles: | 3-pole |
for busbars: | 30, 40, 60, 80, 100, 120 x 10 |
CT can be integrated in the device: | ja |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB |