Part No.: 33514000
QUADRON®60Classic Speed
switch disconnector with fuses, 3-pole
screw M10, connection top, for door coupling rotary handle
size 1
double-breaking
operator independent switching (snap-action mechanism)
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Advantages of the product
With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch)
Also as an Emergency Off switch in combination with the red-yellow door coupling twist handle
CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat busbars
Switched can be installed 90° left/right horizontal, always with the same switch lug position
Product group | 15 |
Subgroup | 23 |
pack size | 1 |
EAN | 4021267335144 |
ECLASS 6.1 | 27371401 |
ECLASS 7.1 | 27371401 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , VDE
type number: QCS-NH1
for fuse links size: | NH 1 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 23 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 250 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B (690V/250A) AC-23A (500V/250A) AC-22A (690V/250A) |
cond. short-circuit current with fuses (AC): | 50 kA / 690V |
approved wth fuse links of operation class: | gG |
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed. | |
System component: degree of protection IP20 at front as per DIN EN 60529, degree of protection near terminal depends on installation; shock protection as per DIN EN 50274 adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe) |
Mechanical data | |
W x H x D: | 184 x 314 x 192 |
weight: | 577,0 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars.
When installing QCS, a busbar support is to be applied left and right, see assembly manual.
Terminal points | |
screw connection | |
M10 | |
screw drive: | SW16 |
Md min.: | 30,0 Nm |
Md max.: | 35,0 Nm |
permitted power dissipation of the fuse-link: | 23 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |