Part No.: 01537000
CRITO®60Classic
connection set, 3-pole, without cover
95 - 300 mm², AWG 3/0 - 600 MCM
for busbars 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Product group | 07 |
Subgroup | 51 |
pack size | 1 |
EAN | 4021267015374 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
CSA , UL , DNV GL
for UL feeder circuits >250V
type number: M300-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
rated current (IEC): | 500 A |
rated voltage (IEC) AC: | 690 V |
rated peak withstand current Ipk max.: | 67.2 kA |
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 1000 V |
max. permitted voltage (IEC) DC: | 1500 V |
current capacity (IEC) max.: | 560 A |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 420 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
for wires UL: | Cu 75°C |
SCCR unprotected max.: | 25 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 200 kA |
SCCR: |
35 kA with any DIVQ/7 circuit breaker 400 A / 600 V AC
200 kA with JDDZ fuse Class L 800 A / 600 V AC 100 kA with JDDZ fuse Class L 1200 A / 600 V AC 200 kA with fuse JDDZ Class J 600 A / 600 V AC 65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
Mechanical data | |
W x H x D: | 153 x 184 x 115 |
weight: | 155,5 kg/100 |
poles: | 3-pole |
for busbars: | 20, 25, 30 x 5, 10 and section busbars |
Terminal points | |
screw clamp connection | |
screw drive: | S8 |
wire stripping: | 38 mm |
min. cross-section: | 95 mm² |
max. cross-section: | 300 mm² |
Md min.: | 24,0 Nm |
Md max.: | 36,0 Nm |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
torque Alu: | Alu: Md 30 - 36 Nm |
min. cross-section UL: | AWG 3/0 |
max. cross-section UL: | MCM 600 |
torque (UL): | 266 lb-in |
for wires UL: | Cu 75°C |
for applications acc. to IEC / EN : |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
The insulation performance of the article depends on the installation conditions. | |
for UL feeder circuits >250V |