Company
Innovations
Products
The picture may show a similar product.
Part No.: 01827 000
busbar connecting terminal 1600 A
50 mm long
for busbars double-T section
System
60Classic
| Product group | 07 |
| Subgroup | 33 |
| pack size | 6 |
| EAN | 4021267018276 |
| ECLASS 6.1 | 27400606 |
| ECLASS 7.1 | 27400606 |
| ETIM 4.0 | EC000713 |
| ETIM 5.0 | EC000713 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: LVH-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 |
| Electrical data IEC | |
| rated voltage (IEC) AC: | 690 V |
| rated peak withstand current Ipk max.: | 72.7 kA |
| rated short-time withstand current Icw (1.0 s) max.: | 51.4 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 2,2 W.
(The power dissipation at full load would be 3,5 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 1000 V |
| max. permitted voltage (IEC) DC: | 1500 V |
| current capacity (IEC) max.: | 1.600 A |
| Details UL | |
| Standards | |
| UL 508 |
| for UL feeder circuits >250V |
| Electrical data UL | |
| rated current (UL): | 1400 A |
| SCCR protected max.: | 65 kA |
| 65 kA in combination with H720-L and any DIVQ/7 1600 A / 480 V AC |
| SCCR: | 30 kA |
| Mechanical data | |
| W x H x D: | 50 x 44 x 43 |
| weight: | 49,4 kg/100 |
| for busbars: | double-T section |
| permitted busbar displacement: | 2 |
| permitted spacing between systems: | 9 - 20 mm |
| Terminal points | |
| screw clamp connection | |
| M8 | |
| Md min.: | 16,0 Nm |
| Md max.: | 24,0 Nm |
| The insulation performance of the article depends on the installation conditions. | |
|
Max. permitted busbar offset 2 mm, 3 units are needed for a 3-pole connection. |
|
| for UL feeder circuits >250V | |
| for a UL-compliant design of the longitudinal busbar connector, the UL separator set 01360 must be used |
01360
000
Set of phase separators for UL installation, 3-pole
for longitudinal connecting terminals 01990, 01823, 01827
105 mm