in-line fuse switch-disconnector 160 A (33235)

The picture may show a similar product.

Description

Part No.: 33235000

in-line fuse switch-disconnector 160 A

screw M8 / clamp 70mm²

size 00

for busbars 30, 40, 50, 60 x 10

System

100Energy

Advantages of the product

Self-closing inspection holes are available in the cover.

Product group 12
Subgroup 51
pack size 1
EAN 4021267332358
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001046
ETIM 5.0 EC001046

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB) , CCC

type number: SLS-00

CCC certificate: 2004010302117261

Technical data

for fuse links size: NH 000, NH 00
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Rated current (IEC): 160 A
rated voltage (IEC) AC: 800 V
rated isolation voltage Ui AC: 1000 V
rated surge voltage Uimp : 8 kV
Utilisation category AC (IEC 60947-3) :

AC22 B (690 V)
AC23 B (400V)
AC23 B (500V / 125A)

AC20 (800 V)

Sichtbarer Hinweis notwendig: Nicht unter Last schalten in Fall von Betriebsspannung höher als 690 V

 

Utilisation category DC (IEC 60947-3) : DC-20B
max. voltage between the fuses: 1000V
visible information required: Do not switch under load.
cond. short-circuit current with fuses (AC): 50 kA / 690 V
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 12.8 W.

(The power dissipation at full load would be 20.0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 1000 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
Degree of protection IP30 at front, degree of protection near terminal depends on installation
Mechanical data
W x H x D: 50 x 455 x 120
weight: 137.0 kg/100
for busbars: 30, 40, 50, 60 x 10

Type of fastening: can be screwed onto drilled busbar,
M8, 12 - 14Nm torque,
or using terminal clamp,
adapter for 185-mm-System,
connection 70mm², screw M8, 12 - 14Nm torque,
connection clamp 1.5-70mm², 3Nm torque
wedge clamp terminal 16-70mm², 3Nm torque

Terminal points
  

screw M8 :
Md 12 - 14 Nm

Application notes

A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.

Reference

with adapter (accessory) for the 185mm-System power

permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.

Links

Downloads

Accessories

03727000
clamp connector
1.5 - 70 mm²
size 00
More

30894000
M8 screw connector
with spring washer
size 00
More

33113000
lateral cover support
for front covers
size 00 - 3
More

33156000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A
More

33224000
prism terminal, single, for Cu cables
16 - 70 mm²
NH 00
More

33238000
terminal clamp
size 00
for: 33235
More

33280000
connection cover
size 00
for: 33234, 33235
More

33300000
mounting clip for current transformator
for adapter SECUR®LeanStreamer
size 00
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com