Part No.: 01823 000
busbar connecting terminal 630 A
40 mm long
for busbars 20, 25, 30 x 5, 10
System
60Classic
| Product group | 07 | 
| Subgroup | 33 | 
| pack size | 6 | 
| EAN | 4021267018238 | 
| ECLASS 6.1 | 27400606 | 
| ECLASS 7.1 | 27400606 | 
| ETIM 4.0 | EC000713 | 
| ETIM 5.0 | EC000713 | 
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
																		 
for UL feeder circuits >250V
type number: LV30-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 | 
| Electrical data IEC | |
| rated voltage (IEC) AC: | 690 V | 
| rated peak withstand current Ipk max.: | 67.1 kA | 
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.3 W.
(The power dissipation at full load would be 0.5 W.)
| Supplementary data IEC | |
| The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. | 
| max. permitted voltage (IEC) AC: | 1000 V | 
| max. permitted voltage (IEC) DC: | 1500 V | 
| current capacity (IEC) max.: | 630 A | 
| Details UL | |
| Standards | |
| UL 508 | 
| for UL feeder circuits >250V | 
| Electrical data UL | |
| rated current (UL): | 756 A | 
| SCCR protected max.: | 65 kA | 
| 65 kA in combination with 30x10-L and any DIVQ/7 800 A / 480 V AC | 
| Mechanical data | |
| W x H x D: | 40 x 37 x 20 | 
| weight: | 25.2 kg/100 | 
| for busbars: | 20, 25, 30 x 5, 10 | 
| permitted busbar displacement: | 2 | 
| permitted spacing between systems: | 13 - 20 mm | 
| Terminal points | |
| screw clamp connection | |
| M12 | |
| Md min.: | 24.0 Nm | 
| Md max.: | 36.0 Nm | 
| The insulation performance of the article depends on the installation conditions. | |
| Max. permitted busbar offset 2 mm, 3 units are needed for a 3-pole connection. | |
| for UL feeder circuits >250V | |
| for a UL-compliant design of the longitudinal busbar connector, the UL separator set 01360 must be used | 
 
						
                01360
        000
        
        
            Set of phase separators for UL installation, 3-pole
            
            
            for longitudinal connecting terminals 01990, 01823, 01827
            105 mm
            