profile terminal (01186)

The picture may show a similar product.

Description

Part No.: 01186000

CRITO®

profile terminal

1200 - 3600 mm²

terminal space 101 x 23-45

for busbars triple-T section

System

60Classic, centre feed unit

Advantages of the product

also rigid copper busbars can be connected if they are installed without mechnical tension

Product group 07
Subgroup 30
pack size 3
EAN 4021267011864
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Approvals

Standards

IEC 61439-1:2020

UL 508

Approvals

CSA , UL

type number: HH101.2

UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
Electrical data IEC
rated current (IEC): 2500 A
rated voltage (IEC) AC: 800 V
rated peak withstand current  Ipk max.: 107 kA
rated short-time withstand current Icw (1.0 s) max.: 51.1 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 1000 V
max. permitted voltage (IEC) DC: 1500 V
current carrying capacity for centre feed: 3’200 A
Details UL
Standards
UL 508
Electrical data UL
rated current (UL): 1800 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR: 25 kA
Mechanical data
W x H x D: 132 x 45 x 154
weight: 172.7 kg/100
for busbars: triple-T section

In order to comply with the required air section as per UL508a, a suitable shrouding must be used.

Terminal points
min. cross-section: 1’600 mm²
max. cross-section: 3’600 mm²
Terminal space: 101 x 23 - 45
Not suitable for aluminium cables !
  

terminal space 101 x 23-45
2 terminal screws M12

Application notes

Not suitable for aluminium cables !
The insulation performance of the article depends on the installation conditions.

Reference

3 terminals are needed for a 3-pole connection. Insert separators when connecting laminated copper busbars in parallel.

Links

Downloads

Accessories

01554000
compartment section, for 3-pole systems
front mounted, 1.10 m long, for holder 01136
3 x 190 x 1100
More

01555000
cover section
top / bottom, 1.10 m long, for holders 01136 or 01137
3 x 109 x 1100
More

01136000
set of holders for cover sections
for 3-pole busbar systems
set consisting of left and right holder, for covers 01554, 01555 and 01417
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
More

01417000
cover section
top / bottom, slotted, 1.10 m long, for holders 01136 or 01137
3 x 118 x 1100
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com