NH fuse switch-disconnector size 000, 125 A (33216)

The picture may show a similar product.

Description

Part No.: 33216000

QUADRON®60Classic

NH fuse switch-disconnector size 000, 125 A

box terminal

connection top or bottom

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

Self-closing inspection holes are available in the cover.

Product group 09
Subgroup 22
pack size 1
EAN 4021267332167
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approvals

IEC (CB) , UL , CCC , DNV GL

for UL feeder circuits >250V

type number: LTS-000

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

CCC certificate: 2004010302117260

Technical data

for fuse links size: NH 000
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 9 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 125 A
rated voltage (IEC) AC: 690 V
rated voltage (IEC) DC: 440 V
rated isolation voltage Ui AC: 800 V
rated isolation voltage Ui DC: 500 V
rated surge voltage Uimp : 6 kV
Utilisation category AC (IEC 60947-3) : AC-21B (690 V / 80 A)
AC-22B (400 V / 125 A)
Utilisation category DC (IEC 60947-3) : DC specifications: 2 current paths (L1,L3) in series
DC-22B (440V/63A)
DC-22B (220V/100A)
DC-21B (440V/80A)
DC-21B (220V/125A)
cond. short-circuit current with fuses (AC): 50 kA / 400 V (125A)
50 kA / 500 V (100A)
50 kA / 690 V (50A)
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6.7 W.

(The power dissipation at full load would be 10.5 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 800 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
In accordance with the specified AC and DC switching properties and in consideration of the overload conditions, certain distances to earthed metal parts are to be adhered to. detailed information upon inquiry

When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed.
Degree of protection IP30 at front, degree of protection near terminal depends on installation
Details UL
Standards
UL 4248-1
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 125 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR: 100 kA
Mechanical data
W x H x D: 89 x 200 x 90
weight: 113.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
front degree of protection: IP30

Type of fastening: patented click mechanism

Terminal points
cage clamp connection
screw drive: S4
wire stripping: 20 mm
min. cross-section: 1.5 mm²
max. cross-section: 50 mm²
Md min.: 3.2 Nm
Md max.: 4.8 Nm
Not suitable for aluminium cables !
  

Box terminal:
2.5 -50mm² flexible cables,
1.5 -50mm² flexible cables with wire-end ferrules
1.5 - 10mm² solid round
16 - 50mm² stranded round
(flexible cables of maximum cross-section may not fit when using wire-end ferrule)
lam. Cu. 6-9 mm wide
Terminal space 10mm x 10mm

Application notes

Not suitable for aluminium cables !
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
permitted power dissipation of the fuse-link: 9 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
for UL feeder circuits >250V

Links

Downloads

Accessories

33051000
lid interlock
for sealing wire
Size 000
More

33156000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A
More

33219000
trim frame, single
130 x 210
size 000
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com