Company
Innovations
Products
The picture may show a similar product.
Part No.: 01035 000
flexible copper busbar, plain, insulated
6x 15.5 x 0.8
350 A, length 2 m
Advantages of the product
The laminated Cu busbars considerably reduce the effort of connecting busbars. The bending devices required for solid copper busbars are unnecessary. The 2mm-thick insulation means that no additional covering is required.
| Product group | 06 |
| Subgroup | 81 |
| pack size | 1 |
| EAN | 4021267010355 |
| ECLASS 6.1 | 27370303 |
| ECLASS 7.1 | 27370303 |
| ETIM 4.0 | EC001522 |
| ETIM 5.0 | EC001522 |
Standards
IEC 61439-1:2020
UL 758
UL 67
Approvals
UL
for UL feeder circuits >250V
type number: 6x15,5x0,8
UL file: E197039, UL category (for USA): QEUY2 https://www.ul.com
UL file 2: E481423, UL category+ (for USA): AVLV2 https://www.ul.com
UL file: E197039, UL category (for Canada): QEUY8 https://www.ul.com
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 |
| Electrical data IEC | |
| rated current (IEC): | 350 A |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 44.4 W.
(The power dissipation at full load would be 69.4 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
current at 30 K : |
257 A |
| current at 40 K: | 306 A |
current at 50 K : |
350 A |
| current at 60 K: | 389 A |
| current at 70 K: | 424 A |
| Details UL | |
| Standards | |
|
UL 758
UL 67 |
| for UL feeder circuits >250V |
| capacity at 50 K: | 375 A |
| Mechanical data | |
| W x H x D: | 20 x 9 x 2000 |
| weight: | 139.2 kg/100 |
| cross-section: | 74.4 mm² |
|
see product description of the used busbar support |
|
capacity depending on the permitted temperature rise of flexible copper busbar without impact of additional heat sources:
|
|
| notice the temperature stability of the insulation of 105 °C take conductors with required cross-section for connection to the products and devices (acc. to relevant standards or manufacturer instructions) |
|
| for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com