Company
Innovationen
Products
The picture may show a similar product.
Part No.: 01602000
universal busbar support
2-pole with internal screw holes
for busbars 12, 20, 30 x 5, 10
System
60Classic
Advantages of the product
With internal screw holes
can also be used as centre support
Product group | 06 |
Subgroup | 06 |
pack size | 1 |
EAN | 4021267016029 |
ECLASS 6.1 | 27400607 |
ECLASS 7.1 | 27400607 |
ETIM 4.0 | EC001166 |
ETIM 5.0 | EC001166 |
Standards
IEC 61439-1:2020
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated voltage (IEC) AC: | 800 V |
rated voltage (IEC) DC: | 1000 V |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 1000 V |
rated isolation voltage Ui DC: | 1000 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.0 W.
(The power dissipation at full load would be 0.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 1500 V |
Short-circuit withstand capacity: Icw up to 39.8kA - 255ms - DC busbar support separation 250 mm (20 x 10 mm busbars) Icw up to 45.7kA - 255ms - DC busbar support separation 400mm (30 x 10mm busbars) |
Mechanical data | |
W x H x D: | 13 x 136 x 45 |
weight: | 8.3 kg/100 |
poles: | 2-pole |
for busbars: | 12, 20, 30 x 5, 10 |
The insulation performance of the article depends on the installation conditions. | |
Reference |
Torque for the screws of the busbar support Md = 4Nm |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com