Seleção de produtos

for UL feeder circuits >250V

sistema básico 125 A (11405)     PCF: 10,43 kg CO2e

A imagem pode mostrar um produto similar.

Descrição

Código da peça: 11405000A

CrossBoard®

sistema básico 125 A

3 polos

405 mm de comprimento, proteção contra contato acidental

com interface CrossLink®

Sistema

CrossBoard® 125A / 250A

Vantagens do produto

all-round touch-safe protected busbar system up to 125 A
mounting to DIN rails with no tools
simple screwing-on to mounting plates
completely pre-assembled and ready to use

Grupo de produto 06
Subgroup 50
Unidade por pacote 1
EAN 4021267114053
ECLASS 6.1 27400613
ECLASS 7.1 27400613
ETIM 4.0 EC001900
ETIM 5.0 EC001900

Aprovações

Standards

IEC 61439-1:2020

UL 508

Approvals

IEC (CB) , UL

for UL feeder circuits >250V

Número de tipo: CB405-24x7

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Aprovação CCC: no certification required

Dados técnicos

Dados IEC
Standards
IEC 61439-1:2020
Dados elétricos IEC
Corrente de medição (IEC): 125 A
Tensão de medição (IEC) AC: 690 V
Tensão nominal de isolamento: 800 V
Tensão suportável nominal de impulso Uimp: 6 kV
rated peak withstand current  Ipk max.: 25 kA
Corrente nominal admissível de curta duração Icw (0,3 s) max.: 10 kA

Dissipação de energia do artigo:

A dissipação de energia em uma carga de 80% resulta em 6,0 W.

(A dissipação de energia em sua carga máxima seria 9,3 W.)

Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

tensão máxima IEC DC: 800 V
Dados UL
Standards
UL 508
for UL feeder circuits >250V
Dados electricos UL
corrente nominal (UL): 100 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
tensão nominal (UL) DC: 600 V
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
with JDDZ fuse Class J 175 A / 600 V AC
SCCR: 65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC
100 kA with JDDZ fuse Class J 175 A / 600 V AC
Dados mecânicos
L x A x P: 405 x 160 x 45
Peso: 137,2 kg/100
Polaridade: 3 polos
degree of protection: IP20

Instruções de Aplicação

Notas

We recommend the use of a high DIN rail (35x15) for optimum stability and maximum load of 4 kg.
For higher loads we recommend to fix the CrossBoard® with screws on a panel.
For the use of the QUADRON®CrossBoard NH fuse switch-disconnector size 000 the CrossBoard® has to be fixed with screws on a panel.
For details please see the mounting instruction.

2 CrossBoards® mounted side by side can get a shared feeding component.

The drilling plan for mounting 2 CrossBoards® side by side is available as Dimensioned drawing #2

for UL feeder circuits >250V

Links

Downloads

Acessórios

11050000A
CrossBar®
mounting rail for accessories
attachable to CrossBoard
for distribution terminals
NEW
Mais

11051000A
CrossBar®
mounting rail for accessories
attachable to CrossBoard
for distribution blocks
para: Phoenix Contact PTFIX
NEW
Mais

Encontre sua pessoa de contato

Para a página de contato

Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil

Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de

Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com