Descrição

Código da peça: 31232000

SECUR®60Classic PowerLiner

seccionador-interruptor-fusível para montagem em barramento

para fusíveis 10x38 IEC 60269-2

3P

connection bottom

para barramentos 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção

comutável de 3 polos / 1 polo

Sistema

60Classic

Grupo de produto 01
Subgroup 42
UE 1
EAN 4021267312329
catalog page 2020 : 3.20
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Aprovações

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

EAC

Número de tipo: SPL-10x38

EAC Type: SPL

Dados técnicos

for fuse links size: 10x38
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 3 W
Dados IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Dados elétricos IEC
Corrente de medição (IEC): 32 A
Tensão de medição (IEC) AC: 690 V
Tensão de medição (IEC) DC: 110 V
Tensão nominal de isolamento: 500 V
rated isolation voltage Ui DC: 250 V
Tensão suportável nominal de impulso Uimp: 6 kV
Utilisation category AC (IEC 60947-3) :

AC-23 A (400 V)
AC-22 A (690 V)

cond. short-circuit current with fuses (AC): 50 kA / 400 V (32A)
approved wth fuse links of operation class: gG

Dissipação de energia do artigo:

A dissipação de energia em uma carga de 80% resulta em 3,4 W.

(A dissipação de energia em sua carga máxima seria 5,3 W.)

Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

tensão máxima IEC AC: 725 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
for fuse links gG and aM as per IEC / EN 60269-2

The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard.

Dados mecânicos
L x A x P: 27 x 220 x 100
Peso: 76,0 kg/100
Polaridade: 3 polos
para barramentos: 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção
front degree of protection: IP20

Type of fastening: patented click mechanism

pontos terminais
cage clamp connection
screw drive: PZ2
wire stripping: 12 mm
min. cross-section: 1,5 mm²
max. cross-section: 16 mm²
Md min.: 2,0 Nm
Md max.: 2,5 Nm
Not suitable for aluminium cables !

Links

Downloads

Acessórios

31901000
módulo de fixação lateral
Mais

31902000
redutor D02 para fusíveis D01 2 - 16 A
Mais

31903000
interruptor de sinalização
comutador 250 V AC / 5 A, 30 V DC / 4 A
Mais

Encontre sua pessoa de contato

Para a página de contato

Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil

Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de

Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com

Produtos Configurador Current metal surcharges folder for files