Seleção de produtos

for UL feeder circuits >250V

terminal de pinças (01135)

A imagem pode mostrar um produto similar.

Descrição

Código da peça: 01135000

CRITO®

terminal de pinças

35 - 150 mm², AWG 2 - 300 MCM,  lam. Cu. 15 - 20 x 5 - 10

para barramentos 12, 15, 20 x 5, 10

Sistema

60Classic, 30Compact 3P

Vantagens do produto

Terminal with captive clamping screws, conductor can be overlapped.
Indication of nominal cross-section and tightening torque noted on the terminal.
Contact between conductor and busbar via cable bed.

Grupo de produto 07
Subgroup 19
UE 6
EAN 4021267011352
catalog page 2020 : 2.2, 3.6
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Aprovações

Standards

IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

UL , EAC

for UL feeder circuits >250V

Número de tipo: 515-L

EAC Type: TE-B

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Aprovação CCC: no certification required

Dados técnicos

Dados IEC
Standards
IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003
Dados elétricos IEC
Corrente de medição (IEC): 275 A
Tensão de medição (IEC) AC: 690 V
The insulation performance of the article depends on the installation conditions.
rated peak withstand current  Ipk max.: 49.8 kA
Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

tensão máxima IEC AC: 1000 V
tensão máxima IEC DC: 1500 V
current capacity (IEC) max.: 480 A
Dados UL
Standards
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Dados electricos UL
rated current (UL): 285 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR: 18 kA
Dados mecânicos
L x A x P: 28 x 34 x 69
Peso: 10,2 kg/100
para barramentos: 12, 15, 20 x 5, 10
pontos terminais
min. cross-section: 35 mm²
max. cross-section: 150 mm²
Área de aperto: 20 x 22
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
  

for applications acc. to IEC / EN :
Cu or Al 35 - 150 mm² stranded round cables and stranded sectored cables
Cu also flexible cables, directly or with wire-end ferrule
(flexible cables of maximum cross-section may not fit when using wire-end ferrule)

for applications acc. to UL / CSA :
Cu 35 - 150 mm² / AWG 2 - MCM 300

Notas

Connections not maintenance-free if aluminium conductors are used (also see catalogue 8.2)

Links

Downloads

Encontre sua pessoa de contato

Para a página de contato