Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31158000
SECUR®60Classic PowerLiner
seccionador-interruptor-fusível D0 para montagem em barramento
para ligações com fusíveis D01 e D02
E18 / 63 A / 3P
connection bottom
para barramentos 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção
comutável de 3 polos / 1 polo
Sistema
60Classic
Grupo de produto | 01 |
Subgroup | 42 |
Unidade por pacote | 1 |
EAN | 4021267311582 |
ECLASS 6.1 | 27142110 |
ECLASS 7.1 | 27142110 |
ETIM 4.0 | EC000277 |
ETIM 5.0 | EC000277 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
VDE , CCC
Número de tipo: SPL-D0
CCC certificate: 2018010302128773
for fuse links size: | D0 |
fuse links acc. to standard: | IEC / HD 60269-3 |
permitted power dissipation of the fuse-link: | 5,5 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 63 A |
Tensão de medição (IEC) AC: | 400 V |
Tensão de medição (IEC) DC: | 110 V |
Tensão nominal de isolamento: | 500 V |
rated isolation voltage Ui DC: | 250 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-23A (400 V) |
Utilisation category DC (IEC 60947-3) : | DC-21B (48V) 1 pole DC-21B (110V) 2 poles |
cond. short-circuit current with fuses (AC): | 50 kA / 400 V |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 6,7 W.
(A dissipação de energia em sua carga máxima seria 10,5 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
for fuse links and gauge rings as per DIN VDE 0636-3 IEC / HD 60269-3 utilisation category as per VDE 0638: AC22 |
|
The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard. |
Dados mecânicos | |
L x A x P: | 27 x 220 x 100 |
Peso: | 75,9 kg/100 |
Polaridade: | 3 polos |
para barramentos: | 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção |
front degree of protection: | IP20 |
Type of fastening: patented click mechanism
pontos terminais | |
cage clamp connection | |
screw drive: | PZ2 |
wire stripping: | 12 mm |
min. cross-section: | 1,5 mm² |
max. cross-section: | 16 mm² |
Md min.: | 2,0 Nm |
Md max.: | 2,5 Nm |
Not suitable for aluminium cables ! | |
frame terminal: |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
Notas |
SECUR®PowerLiner can be fitted with D0 adapter sleeves. With reducer insert (Part no. 31902) and adapter sleeves, also suitable for D01 fuse links. The use of the side module part no. 31901 is recommended for continuous loads of 35 A or greater. |
permitted power dissipation of the fuse-link: | 5,5 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |