chave seccionadora de fusível vertical 400 A (37527)

A imagem pode mostrar um produto similar.

Descrição

Código da peça: 37527000A

QUADRON®185Power

chave seccionadora de fusível vertical 400 A

tamanho 2, comutável 1 polo

V-clamp 120 mm²

terminal body alu, pressure piece brass

prewired with 3x measuring transformers 400 A / 333 mV, accuracy class 1, with lead RJ12 (3,00 m)

para barramentos 30, 40, 60, 80, 100, 120 x 10

coming soon

Sistema

185Power

Vantagens do produto

Self-closing inspection holes are available in the cover.

Cover can be locked when closed.

Grupo de produto 12
Subgroup 64
Unidade por pacote 1
EAN 4021267375270
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001046
ETIM 5.0 EC001046

Aprovações

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB)

Número de tipo: QU185-2 Pre-Assembled

Dados técnicos

for fuse links size: NH 2
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 34 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Dados IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Dados elétricos IEC
Corrente de medição (IEC): 400 A
Tensão de medição (IEC) AC: 800 V
Tensão nominal de isolamento: 1000 V
Tensão suportável nominal de impulso Uimp: 12 kV
Utilisation category AC (IEC 60947-3) :

AC-22B (800 V / 200 A)
AC-22B (690 V / 400 A)
AC-23B (400 V / 400 A)

Utilisation category DC (IEC 60947-3) : DC-20B
max. voltage between the fuses: 1000V
visible information required: Do not switch under load.
cond. short-circuit current with fuses (AC): 100 kA / 690 V (400 A)
120 kA / 400 V (400 A)
65 kA / 800 V (200A)
approved wth fuse links of operation class: gG

Dissipação de energia do artigo:

A dissipação de energia em uma carga de 80% resulta em 38,4 W.

(A dissipação de energia em sua carga máxima seria 60,0 W.)

Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
Besondere Betriebsbedingungen gemäß IEC / EN 61439-1 können zu Fehlauslösungen von Meldeschaltern oder Sicherungsüberwachungen führen. Die vorliegenden Betriebsbedingungen sind dementsprechend bei der Auswertung der Meldesignale zu berücksichtigen.
Degree of protection IP20 at front, degree of protection near terminal depends on installation
Dados mecânicos
L x A x P: 100 x 687 x 189
Peso: 543,0 kg/100
Polaridade: 3 polos
para barramentos: 30, 40, 60, 80, 100, 120 x 10
CT can be integrated in the device: ja
CT can be integrated in the CT module: nein
front degree of protection: IP20
degree of protection when open: IP10

Type of fastening:
can be screwed onto drilled busbar, diameter 13mm, undrilled mounting with terminal clamp
connection:
screw connection M12

pontos terminais
v-clamp
min. cross-section: 25 mm²
max. cross-section: 240 mm²
re: 25 - 95 mm²
rm: 25 - 150 mm²
se: 35 - 240 mm²
sm: 35 - 185 mm²
Suitable for aluminium conductors.
the temperature of aluminium conductors must not exceed 80°C (see operating instructions)
pre-treatment of aluminium conductors: see general technical information (under Downloads)

Instruções de Aplicação

Suitable for aluminium conductors.
the temperature of aluminium conductors must not exceed 80°C (see operating instructions)
pre-treatment of aluminium conductors: see general technical information (under Downloads)
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.

Notas

The terminal compartment cover 33733 is always needed for the connection at top and when using cable lugs.

permitted power dissipation of the fuse-link: 34 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.

Links

Downloads

Acessórios

33740000A
grampo de fixação
para sistemas de barramentos sem coberturas do sistema
tamanho 1 - 3
Mais

33733000A
tampa da área de conexão
universal para trilhos NH tamanho 1 - 3 e trilho de conexão 800 A
tamanho 1- 3
Mais

33738000A
grampo de fixação CrossLink®
para sistemas de barramento com proteção contra contato acidental CrossLink®
tamanho 1 - 3
Mais

33156000
interruptor de sinalização
comutador 250 V AC / 5 A, 30 V DC / 4 A
Mais

33758000A
faixa de rolamento lateral
para coberturas frontais
tamanho 00 - 3
Mais

Encontre sua pessoa de contato

Para a página de contato

Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil

Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de

Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com