Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31281000
AMBUS®Panel
suporte para fusíveis cilíndricos, para fusíveis semicondutores
22 x 58 / 1P
100 A / 690 V
for mounting rail
Sistema
Panel
Vantagens do produto
large clamping range
Grupo de produto | 17 |
Subgroup | 12 |
Unidade por pacote | 6 |
EAN | 4021267312817 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approvals
IEC (CB) , CSA , UL , CCC
for UL feeder circuits >250V
Número de tipo: AES22x58
UL file: E230163, UL category (for USA): IZLT https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com
CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org
CCC certificate: 2012010302584095
for fuse links size: | 22x58 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 11 W |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 100 A |
Tensão de medição (IEC) AC: | 690 V |
Tensão nominal de isolamento: | 800 V |
rated isolation voltage Ui DC: | 800 V |
Tensão suportável nominal de impulso Uimp: | 6 kV |
cond. short-circuit current with fuses (AC): | 100 kA / 500 V (125 A) |
80 kA / 690 V (80 A) | |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 2,2 W.
(A dissipação de energia em sua carga máxima seria 3,5 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
further utilisation category AC (IEC 60947-3): | AC-20B (1000 V) at pollution degree 2 |
further utilisation category DC (IEC 60947-3): | DC-20B (800 V) |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
for fuse links as per IEC / EN 60269-2 with permitted rated power dissipationsup to max. 9.5W for gG/gL up to max. 7W for aM for fuse links aR / gR / gRL under operating conditions up to max. 11W, for which at least 50mm² leads must be connected |
Dados UL | |
Standards | |
UL 4248-1 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Dados electricos UL | |
corrente nominal (UL): | 80 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
tensão nominal (UL) DC: | 600 V |
for wires UL: | Cu 75°C |
SCCR: | 100 kA |
Dados mecânicos | |
L x A x P: | 36 x 115 x 69 |
Peso: | 15,8 kg/100 |
Polaridade: | 1 polo |
Montagem: | for mounting rail |
degree of protection: | IP20 |
front degree of protection: | IP20 |
pontos terminais | |
cage clamp connection | |
wire stripping: | 20 mm |
min. cross-section: | 4 mm² |
max. cross-section: | 50 mm² |
Md min.: | 3,5 Nm |
Md max.: | 4,0 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 10 |
max. cross-section UL: | AWG 1/0 |
torque (UL): | 35 lb-in |
for wires UL: | Cu 75°C |
box terminal : |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 11 W |
for UL feeder circuits >250V |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com