Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 33234000
chave seccionadora de fusível vertical 160 A
parafuso M8/grampo 70 mm²
tamanho 00
para barramentos 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção
Sistema
60Classic
Vantagens do produto
Self-closing inspection holes are available in the cover.
Grupo de produto | 12 |
Subgroup | 50 |
Unidade por pacote | 1 |
EAN | 4021267332341 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001046 |
ETIM 5.0 | EC001046 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , CCC
Número de tipo: SLS-00
CCC certificate: 2004010302117261
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 160 A |
Tensão de medição (IEC) AC: | 690 V |
Tensão nominal de isolamento: | 1000 V |
Tensão suportável nominal de impulso Uimp: | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC-22B (690V) AC-23B (400V) AC-23B (500V/125A) |
Utilisation category DC (IEC 60947-3) : | DC-20B max. voltage between the fuses: 1000V visible information required: Do not switch under load. |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 17,3 W.
(A dissipação de energia em sua carga máxima seria 27,0 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
tensão máxima IEC DC: | 1000 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
Degree of protection IP30 at front, degree of protection near terminal depends on installation |
Dados mecânicos | |
L x A x P: | 50 x 455 x 136 |
Peso: | 146,0 kg/100 |
para barramentos: | 12, 15, 20, 25, 30 x 5, 10 e barramentos de seção |
Type of fastening:
patented click mechanism, connection 70mm², screw M8, 12 - 14Nm torque,
connection
clamp 1.5-70mm², 3Nm torque, wedge clamp terminal 16-70mm², 3Nm torque
pontos terminais | |
screw M8 : |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |