Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 01068000
CRITO®
terminal condutor universal
16 - 120 mm², AWG 6 - 250 MCM
para barramentos barramentos planos 5 mm
Sistema
60Classic, 30Compact 3P
Vantagens do produto
Terminal with integrated holding spring, captive clamping screw and opened terminal space.
Indication of nominal cross-section and tightening torque noted on the terminal.
Grupo de produto | 07 |
Subgroup | 18 |
Unidade por pacote | 25 |
EAN | 4021267010683 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
CSA , UL , DNV GL
Número de tipo: 524
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Aprovação CCC: no certification required
Dados IEC | |
Standards | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Dados elétricos IEC | |
Corrente de medição (IEC): | 250 A |
Tensão de medição (IEC) AC: | 690 V |
rated peak withstand current Ipk max.: | 27.7 kA |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 0,0 W.
(A dissipação de energia em sua carga máxima seria 0,0 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
tensão máxima IEC AC: | 1000 V |
tensão máxima IEC DC: | 1500 V |
current capacity (IEC) max.: | 440 A |
Dados UL | |
Standards | |
UL 508 |
suitable for field-installed conductors |
Dados electricos UL | |
corrente nominal (UL): | 255 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR: | 18 kA |
Dados mecânicos | |
L x A x P: | 24 x 36 x 55 |
Peso: | 10,6 kg/100 |
para barramentos: | barramentos planos 5 mm |
pontos terminais | |
min. cross-section: | 16 mm² |
max. cross-section: | 120 mm² |
Área de aperto: | 17 x 15 |
Md min.: | 12,0 Nm |
Md max.: | 18,0 Nm |
Not suitable for aluminium cables ! | |
16 - 120 mm² / AWG 4 - MCM 250 |
Not suitable for aluminium cables ! | |
The insulation performance of the article depends on the installation conditions. | |
The suitability for feeder circuits (meeting the required feeder spacings) depends on the installation conditions. |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com