Selezione prodotto

for UL feeder circuits >250V

Base per fusibili cilindr. (33307)

The picture may show a similar product.

Descrizione

Cod.art.: 33307000

QUADRON®Panel

Base per fusibili cilindr.

Class J / 3P, morsetti 150 mm²

200 A / 600 V (41x146)

für Montageplatte

Montaggio

Mounting plate

gruppo di prodotto 16
sottogruppo prodotto 12
Pz / conf. 1
EAN 4021267333072
pagina catalogo 2010 : 5.10
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Certificazioni

Norme

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

UL 4248-8

UL 4248-1

Omologazioni

CSA , UL , EAC

for UL feeder circuits >250V

type no.: JC200

EAC Type: AJC

UL file: E230163, UL category (for USA): IZLT https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

Dati tecnici

per fusibili di grandezza: Class J 200 A
fusibile secondo norma: UL 248-8
potenza diss. max. ammissibile del fusibile inserito: 22 W
Details IEC
Norme
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

Valori elettrici

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 4,7 W.

(The power dissipation at full load would be 7,4 W.)

for Class J fuses 110 - 200A as per UL 248-8 (41x146)
Details UL
Norme
UL 4248-8
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
corrente nominale (UL): 200 A
tensione nominale (UL) AC: 600 V
frequenza nominale (UL): 50 / 60 Hz
tensione nominale (UL) DC: 600 V
for wires UL: Cu 75°C
SCCR: 200 kA
Valori meccanici
L x A x P: 210 x 255 x 117
peso: 405,0 kg/100
Poli: 3 poli
Mounting: für Montageplatte
Connessioni
Not suitable for aluminium cables !
for wires UL: Cu 75°C
  

tunnel terminal with hole of 17,0 mm diameter

acc. to IEC / EN :
10 - 150 mm²
flexible cables, directly or with wire-end ferrule,
solid and stranded round cables,
Md 16 - 18 Nm

(flexible cables of maximum cross-section may not fit when using wire-end ferrule)

acc. to UL :
AWG 8 - MCM 300
stranded cables Class B acc. to UL 486E
142 - 160 lb.in.

Avvisi e consigli

Shock protection through push-on covers.

Links

Downloads

Accessori

03219000A
Fusibile 125 A
-Mersen-
600 V AC, fast acting
Class J, 41x146
Di Più

03220000A
Fusibile 150 A
-Mersen-
600 V AC, fast acting
Class J, 41x146
Di Più

03221000
Fusibile 175 A
-Mersen-
600 V AC, fast acting
Class J, 41x146
Di Più

03222000
Fusibile 200 A
-Mersen-
600 V AC, fast acting
Class J, 41x146
Di Più

03233000
Fusibile 125 A
-Mersen-
600 V AC, time delay
Class J, 41x146
Di Più

03234000
Fusibile 150 A
-Mersen-
600 V AC, time delay
Class J, 41x146
Di Più

03235000
Fusibile 175 A
-Mersen-
600 V AC, time delay
Class J, 41x146
Di Più

03236000
Fusibile 200 A
-Mersen-
600 V AC, time delay
Class J, 41x146
Di Più

Similar products

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Prodotti Configuratore Addizionali metalli folder for files