L'Entreprise
Innovationen
Produits
The picture may show a similar product.
Référence 31281000
AMBUS®Panel
support pour fusibles cylindriques, pour fusibles semi-conducteurs
22 x 58 / 1P
100 A / 690 V
for mounting rail
Système
Panel
Avantages produit
large clamping range
Groupe de produits | 17 |
Sous-groupe | 12 |
Dimensions de l'emballage | 6 |
EAN | 4021267312817 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approbations
IEC (CB) , CSA , UL , CCC
for UL feeder circuits >250V
Type: AES22x58
UL file: E230163, UL category (for USA): IZLT https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com
CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org
CCC certificate: 2012010302584095
for fuse links size: | 22x58 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 11 W |
Details IEC | |
Normes | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
Courant assigné (IEC): | 100 A |
Tension assignée (IEC) CA: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated isolation voltage Ui DC: | 800 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
cond. short-circuit current with fuses (AC): | 100 kA / 500 V (125 A) |
80 kA / 690 V (80 A) | |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 2,2 W.
(The power dissipation at full load would be 3,5 W.)
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
further utilisation category AC (IEC 60947-3): | AC-20B (1000 V) at pollution degree 2 |
further utilisation category DC (IEC 60947-3): | DC-20B (800 V) |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. |
for fuse links as per IEC / EN 60269-2 with permitted rated power dissipationsup to max. 9.5W for gG/gL up to max. 7W for aM for fuse links aR / gR / gRL under operating conditions up to max. 11W, for which at least 50mm² leads must be connected |
Details UL | |
Normes | |
UL 4248-1 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 80 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
for wires UL: | Cu 75°C |
Icc: | 100 kA |
Charactéristiques mécaniques | |
L x H x P: | 36 x 115 x 69 |
Poids: | 15,8 kg/100 |
Pôles: | 1 pôle |
Mounting: | for mounting rail |
degree of protection: | IP20 |
front degree of protection: | IP20 |
Points de raccordement | |
cage clamp connection | |
wire stripping: | 20 mm |
min. cross-section: | 4 mm² |
max. cross-section: | 50 mm² |
Md min.: | 3,5 Nm |
Md max.: | 4,0 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 10 |
max. cross-section UL: | AWG 1/0 |
torque (UL): | 35 lb-in |
for wires UL: | Cu 75°C |
bornes à cage : |
Not suitable for aluminium cables ! | |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. | |
permitted power dissipation of the fuse-link: | 11 W |
for UL feeder circuits >250V |