support pour fusibles cylindriques, pour fusibles semi-conducteurs (31281)

The picture may show a similar product.

Description

Référence 31281000

AMBUS®Panel

support pour fusibles cylindriques, pour fusibles semi-conducteurs

22 x 58 / 1P

100 A / 690 V

for mounting rail

Système

Panel

Avantages produit

large clamping range

Groupe de produits 17
Sous-groupe 12
Dimensions de l'emballage 6
EAN 4021267312817
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Homologations

Normes

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approbations

IEC (CB) , CSA , UL , CCC

for UL feeder circuits >250V

Type: AES22x58

UL file: E230163, UL category (for USA): IZLT https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com

CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org

CCC certificate: 2012010302584095

Données techniques

for fuse links size: 22x58
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 11 W
Details IEC
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Courant assigné (IEC): 100 A
Tension assignée (IEC) CA: 690 V
rated isolation voltage Ui AC: 800 V
rated isolation voltage Ui DC: 800 V
Tension assignée de tenue aux chocs Uimp: 6 kV
cond. short-circuit current with fuses (AC): 100 kA / 500 V (125 A)
80 kA / 690 V (80 A)
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 2,2 W.

(The power dissipation at full load would be 3,5 W.)

Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

further utilisation category AC (IEC 60947-3): AC-20B (1000 V) at pollution degree 2
further utilisation category DC (IEC 60947-3): DC-20B (800 V)
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence.
for fuse links as per IEC / EN 60269-2 with permitted rated power dissipationsup to max. 9.5W for gG/gL up to max. 7W for aM for fuse links aR / gR / gRL under operating conditions up to max. 11W, for which at least 50mm² leads must be connected
Details UL
Normes
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 80 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
for wires UL: Cu 75°C
Icc: 100 kA
Charactéristiques mécaniques
L x H x P: 36 x 115 x 69
Poids: 15,8 kg/100
Pôles: 1 pôle
Mounting: for mounting rail
degree of protection: IP20
front degree of protection: IP20
Points de raccordement
cage clamp connection
wire stripping: 20 mm
min. cross-section: 4 mm²
max. cross-section: 50 mm²
Md min.: 3,5 Nm
Md max.: 4,0 Nm
Not suitable for aluminium cables !
  
min. cross-section UL: AWG 10
max. cross-section UL: AWG 1/0
torque (UL): 35 lb-in
for wires UL: Cu 75°C
  

bornes à cage :
4 - 50 mm² / AWG 10 - AWG 1/0
câble souple, direct ou avec embout
Md 3,5 - 4,0 Nm / 31 - 35 lb.in.

(câble souple de section maxi ne convient pas si équipé d'embout)

Application notes

Not suitable for aluminium cables !
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence.
permitted power dissipation of the fuse-link: 11 W
for UL feeder circuits >250V

Links

Documentation

Accessoires

Similar products

31120000
AMBUS®Panel
support pour fusibles cylindriques
22 x 58 / 1P
100 A / 690 V
Plus

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com