L'Entreprise
Innovationen
Produits
for UL feeder circuits >250V
The picture may show a similar product.
Référence 11300000A
CrossBoard®
système de base 250 A
3 pôles
300 mm de long, protection contre le contact
avec interface CrossLink®
Nouveau
Système
CrossBoard®
Avantages produit
touch-safe protected busbar system up to 250 A
rear feedable
plug and play
easy to screw to mounting plates
completely pre-assembled and immediately ready for use
Groupe de produits | 06 |
Sous-groupe | 50 |
Dimensions de l'emballage | 1 |
EAN | 4021267113001 |
ECLASS 6.1 | 27400613 |
ECLASS 7.1 | 27400613 |
ETIM 4.0 | EC001900 |
ETIM 5.0 | EC001900 |
Normes
IEC 61439-1:2020
UL 508
Approbations
IEC (CB) , UL
for UL feeder circuits >250V
Type: CB-XL-300-24x16
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 |
Electrical data IEC | |
Courant assigné (IEC): | 250 A |
Tension assignée (IEC) CA: | 690 V |
rated isolation voltage Ui AC: | 800 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
rated peak withstand current Ipk max.: | 30 kA |
rated short-time withstand current Icw (0.1 s) max.: | 15 kA |
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Tension maximale IEC CC: | 800 V |
Details UL | |
Normes | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 250 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
100 kA with JDDZ fuse Class J 400 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
Charactéristiques mécaniques | |
L x H x P: | 300 x 160 x 45 |
Poids: | 129,8 kg/100 |
Pôles: | 3 pôles |
degree of protection: | IP20 |
Conseils |
Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation |
for UL feeder circuits >250V |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com