L'Entreprise
Innovationen
Produits
The picture may show a similar product.
Référence 33422000
QUADRON®60Classic
porte-fusible Class J monté sur rail, raccordement par le haut / par le bas
pour fusibles Class J, 35 - 60 A (27x60)
3P, avec borne à cage
raccordement par le haut ou par le bas
pour jeux de barres 12, 15, 20, 25, 30 x 5, 10 et barres profilées
Système
60Classic
Avantages produit
the product is based on the UL approval in category IZLT2 also listed in category NMTR (file E123577)
CrossLink® adapter technology
Fast and safe conversion of the connection for top or bottom; the parts under voltage remain shock protected Simple and safe clicking into place and making contact
Safe connection through shock protection split into 2
Busbar supports for flat busbars can be mounted above each other
Groupe de produits | 16 |
Sous-groupe | 24 |
Dimensions de l'emballage | 1 |
EAN | 4021267334222 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Normes
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H
UL 4248-8
UL 4248-1
Approbations
UL
for UL feeder circuits >250V
Type: QCC-ClassJ60A
UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com
UL file 2: E123577, UL category+ (for USA): NMTR https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT8 https://www.ul.com
UL file 2: E123577, UL category+ (for Canada): NMTR7 https://www.ul.com
for fuse links size: | Class J 60 A |
fuse links acc. to standard: | UL 248-8 |
permitted power dissipation of the fuse-link: | 7 W |
Details IEC | |
Normes | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016, Fuse system H |
Charactéristiques électriques
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 2,3 W.
(The power dissipation at full load would be 3,5 W.)
System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe) |
Details UL | |
Normes | |
UL 4248-8
UL 4248-1 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 60 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
for wires UL: | Cu 75°C |
Icc: | 200 kA |
Charactéristiques mécaniques | |
L x H x P: | 106 x 200 x 135 |
Poids: | 135,0 kg/100 |
Pôles: | 3 pôles |
pour jeux de barres: | 12, 15, 20, 25, 30 x 5, 10 et barres profilées |
Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars
Points de raccordement | |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 14 |
max. cross-section UL: | AWG 2/0 |
for wires UL: | Cu 75°C |
AWG 12 - AWG 2/0 stranded, equivalent 3,3 - 67,4 mm² |
Not suitable for aluminium cables ! | |
permitted power dissipation of the fuse-link: | 7 W |
for UL feeder circuits >250V |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com