L'Entreprise
Innovations
Produits
The picture may show a similar product.
Référence 01513000
CRITO®
attache de profilé
320 - 800 mm²
bornier 41 x 23-45
pour jeux de barres profil en triple T
Système
60Classic, centre feed unit
Avantages produit
also rigid copper busbars can be connected if they are installed without mechnical tension
Groupe de produits | 07 |
Sous-groupe | 30 |
Dimensions de l'emballage | 3 |
EAN | 4021267015138 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Normes
IEC 61439-1:2020
UL 508
Approbations
CSA , UL
Type: HH41.2
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 |
Electrical data IEC | |
Courant assigné (IEC): | 1600 A |
Tension assignée (IEC) CA: | 690 V |
rated peak withstand current Ipk max.: | 81.9 kA |
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Tension maximale IEC CA: | 1000 V |
Tension maximale IEC CC: | 1500 V |
Tenue au courant avec alimentation au milieu: | 1 600 A |
Details UL | |
Normes | |
UL 508 |
Electrical data UL | |
rated current (UL): | 1200 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
Icc: | 25 kA |
Charactéristiques mécaniques | |
L x H x P: | 72 x 45 x 154 |
Poids: | 105,0 kg/100 |
pour jeux de barres: | profil en triple T |
In order to comply with the required air section as per UL508a, a suitable shrouding must be used.
Points de raccordement | |
min. cross-section: | 640 mm² |
max. cross-section: | 1 200 mm² |
Alvéole de serrage: | 41 x 23 - 45 |
Not suitable for aluminium cables ! | |
terminal space 41 x 23-45 |
Not suitable for aluminium cables ! | |
Les performances d'isolation de l'article dépendent des conditions d'installation. | |
Conseils |
3 terminals are needed for a 3-pole connection. Insert separators when connecting laminated copper busbars in parallel. |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com