Innovaciones
Productos
La imagen puede mostrar un producto similar.
Part No.: 33321 000
seccionador vertical doble, 1250 A
tornillo M12, conmutación tripolar
no longer available
ventajas del producto
Self-closing inspection holes are available in the cover.
Strips are equipped with arc chambers.
Cover can be locked when closed.
| grupo de producto | 12 |
| subgrupo | 55 |
| embalaje | 1 |
| EAN | 4021267333218 |
| ECLASS 6.1 | 27142109 |
| ECLASS 7.1 | 27142109 |
| ETIM 4.0 | EC001046 |
| ETIM 5.0 | EC001046 |
Normas
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
homologaciónes
IEC (CB) , CCC
tipo: SLS3
CCC certificate: 2004010302117259
| potencia disipada del fusible permitida: | 48 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
| tamaño: | NH 3 |
| datos IEC | |
| Normas | |
|
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
| datos electricos IEC | |
| intensidad de corriente nominal (IEC): | 1250 A |
| tensión nominal (IEC) AC: | 690 V |
| tensión nominal de aislamiento Ui AC: | 1000 V |
| tensión de pico Uimp: | 8 kV |
| Utilisation category AC (IEC 60947-3) : | AC-20B (690 V) |
| corriente de cortocircuito condicional con fusibles (AC): | 50 kA / 690 V |
| aprobado con fusibles de característica: | gG |
disipación de potencia del articulo:
The power dissipation at a typical load of 80 % results to 148,5 W.
(The power dissipation at full load would be 232,0 W.)
| datos adicionales IEC | |
|
Los siguientes valores han sido verificados con los test bajo ciertas condiciones. Por favor, pregunte a Wöhner por estas condiciones antes de diseñar su cuadro. |
| Seccionadores de fusibles y bases seccionables según IEC 30947-3 solo se podrán usar con una mayor tensión a la nominal , hasta el valor de aislamiento, si son sados como simples bases portafusibles (sin función de seccionamiento), y si viene indicado bien visible sobre el mismo producto. |
| Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
| Degree of protection IP30 at front, degree of protection near terminal depends on installation |
| datos mecánicos | |
| An x A x P: | 199 x 840 x 197 |
| peso: | 1400,0 kg/100 |
Type of fastening:
can be screwed onto drilled busbar, diameter 13mm, undrilled drilling with terminal clamp
connection:
screw connection M12 / 4 x 240mm², SW19, 35Nm torque
| puntos de apriete | |
|
screws M 12 / 4x240mm², wrench size 19, 35 Nm |
|
| Seccionadores de fusibles y bases seccionables según IEC 30947-3 solo se podrán usar con una mayor tensión a la nominal , hasta el valor de aislamiento, si son sados como simples bases portafusibles (sin función de seccionamiento), y si viene indicado bien visible sobre el mismo producto. | |
| potencia disipada del fusible permitida: | 48 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
33156
000
interruptor de señalización
conmutador 250 V AC / 5 A, 30 V DC / 4 A
Mas
Busca tu contacto
a la pagina de contactos
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com