borne en pinza (01760)

La imagen puede mostrar un producto similar.

Descripción

Part No.: 01760000

CRITO®

borne en pinza

Cu / Al 95 - 300 mm²

para barras 20, 25, 30 x 5, 10 y barras perfiladas

sistema

60Classic, centre feed unit, 100Energy

grupo de producto 07
subgrupo 25
embalaje 3
EAN 4021267017606
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Homologaciónes

Normas

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

homologaciónes

CSA , UL , DNV GL

tipo: 529

UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

Homologación CCC: no es obligatoria la certificación

Datos técnicos

datos IEC
Normas
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
datos electricos IEC
intensidad de corriente nominal (IEC): 500 A
tensión nominal (IEC) AC: 690 V
resistencia a corriente de pico Ipk máx. : 81.4 kA
resistencia a corriente de pico en tiempo determinado Icw (1,0 s) max.: 26.1 kA
datos adicionales IEC

Los siguientes valores han sido verificados con los test bajo ciertas condiciones. Por favor, pregunte a Wöhner por estas condiciones antes de diseñar su cuadro.

tensión máxima (IEC) AC: 1000 V
tensión máxima (IEC) DC: 1500 V
máxima intensidad de corriente (IEC): 600 A
datos UL
Normas
UL 508
suitable for field-installed conductors
datos electricos UL
intensidad de corriente nominal (UL): 420 A
tensión nominal (UL) AC: 600 V
frecuencia nominal (UL): 50 / 60 Hz
for wires UL: Cu 75°C
SCCR unprotected max.: 14 kA
1-pole, 3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 65 kA
SCCR: 65 kA with any DIVQ/7 circuit breaker 1200 A / 480 V AC
datos mecánicos
An x A x P: 40 x 49 x 88
peso: 42,5 kg/100
para barras: 20, 25, 30 x 5, 10 y barras perfiladas
puntos de apriete
screw clamp connection
screw drive: S8
wire stripping: 38 mm
min. cross-section: 95 mm²
max. cross-section: 300 mm²
Md min.: 24,0 Nm
Md max.: 36,0 Nm
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
torque Alu: Alu: Md 30 - 36 Nm
  
min. cross-section UL: AWG 3/0
max. cross-section UL: MCM 600
torque (UL): 266 lb-in
for wires UL: Cu 75°C
  

for applications acc. to IEC / EN :
Cu 95 - 300 mm² stranded round cables and stranded sectored cables as well as flexible cables (directly)
Cu 240 - 300 mm² fine stranded flexible cables (directly)
Al 120 - 300 mm² stranded round cables and stranded sectored cables
Al 120 - 240 mm² solid sectored cables

for applications acc. to UL / CSA :
Cu 95 - 300 mm² / AWG 3/0 - MCM 600

Application notes

Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
La capacidad de aislamiento del artículo depende de las condiciones de la instalación.

Links

Downloads

Busca tu contacto

a la pagina de contactos

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com