Innovationen
Productos
La imagen puede mostrar un producto similar.
Part No.: 32592000
EQUES®60Classic
adaptador para embarrado de 210 A, 3 polos
105 x 240
Conexión al sistema por arriba
para Terasaki S250-NJ
para barras 12, 15, 20, 25, 30 x 5, 10 y barras perfiladas
sistema
60Classic
grupo de producto | 05 |
subgrupo | 36 |
embalaje | 1 |
EAN | 4021267325923 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Normas
IEC 61439-1:2020
UL 508
homologaciónes
CSA , UL , DNV GL
for UL feeder circuits >250V
tipo: EPC60250-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Homologación CCC: no es obligatoria la certificación
datos IEC | |
Normas | |
IEC 61439-1:2020 |
datos electricos IEC | |
intensidad de corriente nominal (IEC): | 210 A |
tensión nominal (IEC) AC: | 690 V |
tensión nominal de aislamiento Ui AC: | 800 V |
tensión de pico Uimp: | 6 kV |
disipación de potencia del articulo:
The power dissipation at a typical load of 80 % results to 11,5 W.
(The power dissipation at full load would be 18,0 W.)
datos UL | |
Normas | |
UL 508 |
for UL feeder circuits >250V |
datos electricos UL | |
intensidad de corriente nominal (UL): | 250 A |
tensión nominal (UL) AC: | 600 V |
frecuencia nominal (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 22 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 200 kA |
SCCR: |
150 kA with 3VA61 150 A, 3VA62 250 A / 480 V AC
50 kA with 3VA61 150 A, 3VA62 250 A / 600 V AC 200 kA with 3VA61 150 A, 3VA62 250 A / 240 V AC |
datos mecánicos | |
An x A x P: | 105 x 240 x 35 |
peso: | 102,0 kg/100 |
Polaridad: | 3 polos |
para barras: | 12, 15, 20, 25, 30 x 5, 10 y barras perfiladas |
There must be a clearance of at least 10 mm above the article to remove it from the busbar system. | |
Notas |
combination of busbar adapter 210 A 32592 with MCCB Terasaki S250-NJ tested with allowable threshold value according to standard IEC/EN 60947-1: - individual arrangement, connection top: Ith = 190 A (Rf = 0,75) - individual arrangement, connection bottom: Ith = 210 A (Rf = 0,85) |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB |
for UL feeder circuits >250V |