for UL feeder circuits >250V

in-line fuse switch-disconnector 400 A (33722)

The picture may show a similar product.

Description

Part No.: 33722000A

QUADRON®185Power

in-line fuse switch-disconnector 400 A

screw M12

size 2, 3-pole switchable, with fuse monitoring

for busbars 30, 40, 60, 80, 100, 120 x 10

System

185Power

Advantages of the product

Self-closing inspection holes are available in the cover.

Cover can be locked when closed.

Product group 12
Subgroup 54
pack size 1
EAN 4021267337223
catalog page 2020 : 4.11, 4.12
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001046
ETIM 5.0 EC001046

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB) , CCC , EAC

type number: QU185-2

EAC Type: NH

CCC certificate: 2015010302769224

Technical data

for fuse links size: NH 2
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 34 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Rated current (IEC): 400 A
rated voltage (IEC) AC: 400 V
rated isolation voltage Ui AC: 400 V
rated surge voltage Uimp : 4 kV
Utilisation category AC (IEC 60947-3) :

AC-23B 400A/400V
AC-22B 400A/500V
AC-22B 400A/690V
AC-21B 400A/690V

cond. short-circuit current with fuses (AC): 120 kA / 400 V
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 38.4 W.

(The power dissipation at full load would be 60.0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
Degree of protection IP20 at front (see mounting instruction)
Mechanical data
W x H x D: 100 x 670 x 189
weight: 540.0 kg/100
poles: 3-pole
for busbars: 30, 40, 60, 80, 100, 120 x 10
CT can be integrated in the device: ja
CT can be integrated in the CT module: ja
front degree of protection: IP20

Type of fastening:
can be screwed onto drilled busbar, diameter 13mm, undrilled mounting with terminal clamp
connection:
screw connection M12

Terminal points
  

screw M12 :
Md 30 Nm

Links

Downloads

Accessories

33735000A
box terminal
für Cu / Al 70 - 240 mm²
size 1 - 3
More

33733000A
terminal compartment cover
universal for NH-rails size 1 - 3 and connection rail 800 A
size 1- 3
More

33738000A
CrossLink® terminal clamp
for busbar systems with CrossLink® touch-safe protection
size 1 - 3
More

33740000A
terminal clamp
for busbar systems without system covers
size 1 - 3
More

33156000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A
More

33758000A
lateral bearing strip
for front covers
size 00 - 3
More

33736000A
box terminal
für Cu / Al 120 - 300 mm²
size 1-3
More

33761000A
rear touch-safe protection cover
rear protection for Phase L1
More

33762000A
universal current transformer module
for mounting in the connection compartment
size 1 - 3
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files