Company
Innovationen
Products
The picture may show a similar product.
Part No.: 32278000A
EQUES®185Power
basic system adapter 2x 160 A
for CrossBoard® products
for systems with drilled busbars
for busbars 30, 40, 60, 80, 100, 120 x 10
with CrossLink® interface
NEW
System
185Power
Advantages of the product
Schienenträger überbaubar (in Systemen mit und ohne Crosslink Berührungsschutzabdeckungen)
Product group | 05 |
Subgroup | 48 |
pack size | 1 |
EAN | 4021267322786 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: EQ185-A320-S
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
Rated current (IEC): | 320 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 1000 V |
rated isolation voltage Ui DC: | 1500 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 31,1 W.
(The power dissipation at full load would be 48,6 W.)
Observe the important instructions regarding short-circuit capacity when using CrossBoard® components | |
|
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 320 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 65 kA |
SCCR: |
35 kA with any DIVQ/7 circuit breaker 125 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 125 A / 480 V AC |
Mechanical data | |
W x H x D: | 99 x 670 x 103 |
weight: | 247,0 kg/100 |
poles: | 3-pole |
for busbars: | 30, 40, 60, 80, 100, 120 x 10 |
Mounting: | for systems with drilled busbars |
CT can be integrated in the device: | ja |
front degree of protection: | IP20 |
vertical installation position: | Yes |
horizontal installation position: | No |
short-circuit withstandability: | determined by the mounted components |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com