Part No.: 36130000A
MOTUS®CrossBoard
hybrid motor starter, 3-pole
electronic unit direct and reversing starter 0.18 - 3.0 A / switch for resistive loads 0.18 - 3.0 A
with IO-Link interface
with CrossLink® interface
NEW
System
CrossBoard® 125A / 250A
Product group | 21 |
Subgroup | 01 |
pack size | 1 |
EAN | 4021267361303 |
ECLASS 6.1 | 27370804 |
ECLASS 7.1 | 27370804 |
ETIM 4.0 | EC001037 |
ETIM 5.0 | EC001037 |
Standards
IEC 60947-1:2007 + A1:2010 + A2:2014
IEC 60947-4-2:2011
IEC 61508-1:2010
ISO 13849-1:2015
UL 60947-1
Approvals
UL
for UL feeder circuits >250V
type number: 36130
UL file: E360470, UL category (for USA): NLDX https://www.ul.com
UL file: E360470, UL category (for Canada): NLDX7 https://www.ul.com
Details IEC | |
Standards | |
IEC 60947-1:2007 + A1:2010 + A2:2014 IEC 60947-4-2:2011 IEC 61508-1:2010 ISO 13849-1:2015 |
Electrical data IEC | |
Rated current (IEC): | 3 A |
rated voltage (IEC) AC: | 500 V |
min. operating voltage AC: | 42 V |
trigger characteristic: | Class 10 |
set nominal current: | Yes |
min. load current: | 0.18 A |
max. switching frequency: | 2 Hz |
switching cycles: | 30.000.000 |
safety level: | SIL3 |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 550 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 3,8 W.
(The power dissipation at full load would be 6,0 W.)
Details UL | |
Standards | |
UL 60947-1 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 3 A |
rated voltage (UL) AC: | 500 V |
min. operating voltage AC: | 42 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: | 100 kA with JDDZ fuse Class J 175 A / 600 V AC |
Mechanical data | |
W x H x D: | 22.5 x 160 x 120 |
weight: | 51,4 kg/100 |
poles: | 3-pole |
degree of protection: | IP20 |
vertical installation position: | Yes |
horizontal installation position: | No |
Terminal points | |
screw clamp connection | |
screw drive: | 0,8x4 |
wire stripping: | 8 mm |
min. cross-section: | 0,2 mm² |
max. cross-section: | 2,5 mm² |
Md min.: | 0,5 Nm |
Md max.: | 0,6 Nm |
min. cross-section UL: | AWG 24 |
max. cross-section UL: | AWG14 |
torque (UL): | 5,0 - 7,0 lb-in |
permitted degree of polution: | 2 |
for UL feeder circuits >250V |