Part No.: 32067000A
EQUES®60Classic
busbar adapter 250 A, 4-pole
140 x 270
N on left side
connection to the system top
for Siemens 3VA12, 3VA20, 3VA21, 3VA22, 3VA61, 3VA62
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Product group | 05 |
Subgroup | 36 |
pack size | 1 |
EAN | 4021267320676 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
CSA , UL , DNV GL
for UL feeder circuits >250V
type number: EPC60250-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 250 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 8.1 W.
(The power dissipation at full load would be 12.6 W.)
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 250 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 22 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 200 kA |
SCCR: |
50 kA with 3VA61 150 A, 3VA62 250 A / 600 V AC
200 kA with 3VA61 150 A, 3VA62 250 A / 240 V AC 150 kA with 3VA61 150 A, 3VA62 250 A / 480 V AC |
Mechanical data | |
W x H x D: | 140 x 270 x 35 |
weight: | 153.0 kg/100 |
poles: | 3-pole+N |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
There must be a clearance of at least 10 mm above the article to remove it from the busbar system. | |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB |
for UL feeder circuits >250V |