Part No.: 33398000
QUADRON®60Classic
NH fuse switch-disconnector size 00, 160 A
screw M8
connection top or bottom
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
with CrossLink®Technology
System
60Classic
Advantages of the product
CrossLink® adapter technology
Fast and safe conversion of the connection for top or bottom; the parts under voltage remain shock protected
Simple and safe clicking into place and making contact
Safe connection through shock protection split into 2
Busbar supports for flat busbars can be mounted above each other
Product group | 09 |
Subgroup | 24 |
pack size | 1 |
EAN | 4021267333980 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approvals
IEC (CB) , UL , VDE , CCC , DNV GL
for UL feeder circuits >250V
type number: QCB-NH00
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 160 A |
rated voltage (IEC) AC: | 690 V |
rated voltage (IEC) DC: | 440 V |
rated isolation voltage Ui AC: | 800 V |
rated isolation voltage Ui DC: | 500 V |
rated surge voltage Uimp : | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-21B (690V) AC-22B (500V) AC-20B (1000V) at pollution degree 2 visible information required if used at more than 690V AC: do not switch under load |
Utilisation category DC (IEC 60947-3) : | DC specifications: 2 current paths (L1,L3) in series DC-21B (220V) DC-21B (440V/100A) DC-22B (220V/63A) DC-20B (1000V) at pollution degree 2 visible information required if used at more than 440V DC: do not switch under load |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
80 kA / 500 V (160 A) | |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 11.3 W.
(The power dissipation at full load would be 17.7 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 800 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
In accordance with the specified AC and DC switching properties and in consideration of the overload conditions, certain distances to earthed metal parts are to be adhered to. detailed information upon inquiry When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed. |
|
System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe) |
Details UL | |
Standards | |
UL 4248-1 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 160 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR: | 100 kA |
Mechanical data | |
W x H x D: | 106 x 200 x 97 |
weight: | 103.0 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
front degree of protection: | IP30 |
Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars
Terminal points | |
screw connection | |
M8 | |
screw drive: | SW13 |
Md min.: | 8.0 Nm |
Md max.: | 10.0 Nm |
Not suitable for aluminium cables ! |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
for UL feeder circuits >250V |