Select product

for UL feeder circuits >250V

power distribution platform 125 A (11225)

The picture may show a similar product.

Description

Part No.: 11225

CrossBoard®225

power distribution platform 125 A

3-pole

225 mm long, touch-safe protected, with CrossLink® interface

System

CrossBoard®

Product group 06
Subgroup 50
pack size 1
EAN 4021267112257

Advantages of the product

all-round touch-safe protected busbar system up to 125A
mounting to DIN rails with no tools
simplae screwing-on to mounting plates
completly pre-assembled and ready to use

catalog page 2020 : 1.1
eCl@ss 6.1 27400607
eCl@ss 7.1 27400607
ETIM 4.0 EC001166
ETIM 5.0 EC001166

Approvals

Standards

IEC 61439-1:2011
GB/T 7251.1

Approvals

IEC (CB) , UL , EAC

for UL feeder circuits >250V

type number: CB225-24x7

EAC Type: CB

UL file: E123577, UL category (for USA): NMTR http://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 http://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2011
GB/T 7251.1
Electrical data IEC
Rated current (IEC): 125 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV
rated short-time withstand current Icw (0.3 s) max.: 10 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % of the rated current results to 3.4 W.

(The power dissipation for operation with rated current would be 5.3 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 800 V
rated peak withstand current  Ipk max.: 25 kA
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 100 A
rated voltage (UL) AC: 600 V
rated voltage (UL) DC: 600 V
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 100 kA with JDDZ fuse Class J 175 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC
65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
Mechanical data
W x H x D: 225 x 160 x 45.1
weight: 79.8 kg/100
poles: 3-pole
degree of protection: IP20

Reference

We recommend the use of a high DIN rail (35x15) for optimum stability and maximum load of 4 kg.
For higher loads we recommend to fix the CrossBoard® with screws on a panel.
For the use of the QUADRON®CrossBoard NH fuse switch-disconnector size 000 the CrossBoard® has to be fixed with screws on a panel.
For details please see the mounting instruction.

2 CrossBoards® mounted side by side can get a shared feeding component.

The drilling plan for mounting 2 CrossBoards® side by side is available as Dimensioned drawing #2

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.com

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files