Select product

for UL feeder circuits >250V

hybrid switch, 3-pole or 1-pole switchable (36158)

The picture may show a similar product.

Description

Part No.: 36158000A

OMUS®60Classic

hybrid switch, 3-pole or 1-pole switchable

switch for resistive loads 20.0 A, for applications UL

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

for resistive loads

with CrossLink®Technology

System

60Classic

Advantages of the product

Up to 25A continuous current, including power monitoring
3 phase switching or independent phase switching is possible
Built-in functions for energy supply, fuse protection and switching
More than 30 million operating cycles through hybrid technology

Product group 21
Subgroup 18
pack size 1
EAN 4021267361587
catalog page 2020 : 3.16
ECLASS 6.1 27370804
ECLASS 7.1 27370804
ETIM 4.0 EC001037
ETIM 5.0 EC001037

Approvals

Standards

IEC 60947-1:2007 + A1:2010 + A2:2014
IEC 60947-4-3:2014

UL 60947-1

Approvals

IEC (CB) , UL , EAC

for UL feeder circuits >250V

type number: OM25-H-60

EAC Type: OM

UL file: E483362, UL category (for USA): NRNT https://www.ul.com

UL file: E483362, UL category (for Canada): NRNT7 https://www.ul.com

Technical data

Details IEC
Standards
IEC 60947-1:2007 + A1:2010 + A2:2014
IEC 60947-4-3:2014
Electrical data IEC
Rated current (IEC): 20 A
rated voltage (IEC) AC: 400 V
min. operating voltage AC: 42 V
min. load current: 2 A
max. switching frequency: 1 Hz
reply contact: 1 NO + 1 CO
rated frequency (IEC): 50 Hz
rated isolation voltage Ui AC: 500 V
rated surge voltage Uimp : 2.5 kV
cond. short-circuit current with fuses (AC): 30 kA / 400 V

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 12.8 W.

(The power dissipation at full load would be 20.0 W.)

Details UL
Standards
UL 60947-1
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 20 A
rated voltage (UL) AC: 480 V
min. operating voltage AC: 42 V
rated frequency (UL): 50 / 60 Hz
SCCR protected max.: 30 kA
with JDDZ fuse Class CC 30 A / 480 V AC
Mechanical data
W x H x D: 36 x 200 x 144
weight: 45.8 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
degree of protection: IP20
vertical installation position: Yes
horizontal installation position: No
permitted degree of polution: 2
Terminal points
screw clamp connection
min. cross-section: 1.5 mm²
max. cross-section: 6 mm²
Md min.: 0.5 Nm
Md max.: 0.8 Nm
  
min. cross-section UL: AWG 16
max. cross-section UL: AWG 8
torque (UL): 7 lb-in

Reference

komplett mit Sammelschienenadapter, Last- und Steuerstecker

Links

Downloads

Accessories

36156000A
spare part busbar adapter 25 A
busbar adapter base
for busbars: 12, 15, 20, 25, 30 x 10  and section busbars
More

31189000
cylindr. fuse link 32 A
400 V, gG
10 x 38
More

31252000
cylindr. fuse link 30 A
-Mersen-
600 V AC, time delay
Class CC
for control transformer applications
More

31080000A
cylindr. fuse link 30 A
-Mersen-
600 V AC, time delay
Class CC
for motor load applications
NEW
More

36154000A
OMUS®CrossBoard
hybrid switch, 3-pole or 1-pole switchable
electronic unit switch for resistive loads 25.0 A, for applications IEC
for resistive loads
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files